Permit NumberFIR16-00087
StatusFinaled
Name RELIANCE ELECTRIC
Site Address 3050 S SHOSHONE ST
Project NameHoliday Inn Express
Customer Number 
ePlanReviewYes
Description
Provide a fire alarm system with sprinkler monitoring, elevator recall and shunt and low frequency audible notification in all sleeping units. Full notification is provided in accessible units and common / public areas. Detection is being provided in corridors leading to sleeping units and in floor 1 common areas.

Provide a fire alarm system with sprinkler monitoring, elevator recall and shunt and low frequency audible notification in all sleeping units. Full notification is provided in accessible units and common / public areas. Detection is being provided in corridors leading to sleeping units and in floor 1 common areas.

Associated building permit: BLD15-00516.

Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/1/20169/2/20169/2/2016APASS
DetailsTroy Cobbley
Permit finaled. Seth Phone #: ###-####
CHANGE STATUS TO (ISS)  8/12/2016 DONE
INSP-Final Inspection8/8/20168/9/20168/9/2016APART
DetailsTroy Cobbley
A temporary occupancy is ok for life safety with Scott's permission. I need as-builts, testing of elevator car #1 and the map at the facp.
Miscellaneous action  8/9/2016 DONE
EJ called to say he needs the work flow reopened to upload changes to floor plans & notification.
Plan Modification Accepted  8/9/2016  
Plan mod received for numerous design changes.
CHANGE STATUS TO (REV)  8/9/2016 DONE
Changed to review status for plan mod submittal.
Alarm Plan Check8/9/2016 8/9/2016 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  8/9/2016 DONE
Plan mod approved. No additional review comments.
INSP-Alarm Testing8/5/20168/8/20168/8/2016ADONE
DetailsTroy Cobbley
Need data sheets, breaker locks and locations, test flow switches, test outside alarm bell, document box, map at the facp, test elevator recall
INSP-Final Inspection8/5/20168/5/20168/5/2016PFAIL
DetailsTroy Cobbley
Due to problems on the fire alarm system todays inspection was a walk through of the devices on the 4th and 3rd floors. I noted the need for as-builts due to added smoke detectors and the need for weather proof back boxes on the audio/visual devices installed in the restrooms with showers. Contractor did not have any of the small documents which included the data sheets and review notes.
Miscellaneous action  3/3/2016 DONE
Emailed EJ to let him know NAC calculations were not accurate. Requested he make corrections and submit them.
Alarm Plan Check3/3/2016 3/3/2016 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  3/3/2016 DONE
Resubmittal approved with review comments.
Permit Ready to Issue  3/3/2016 DONE
Issue and Print Permit  3/3/2016 DONE
Inspection Record Card- Fire3/3/2016 3/3/2016 DONE
DetailsChristina Prado
Plan resubmittals received  3/2/2016 DONE
Plan assigned to (Lee)2/11/2016 2/11/2016 DONE
DetailsLee G Meredith
1st review completed  2/11/2016 FAIL
See 1st review comments.
Miscellaneous action  2/11/2016 DONE
Emailed applicant the 1st plan review comments.
Application received  2/9/2016 DONE
Application submitted via PDS Online on Feb 9 2016 4:17PM