Permit Information
Permit NumberFIR16-00097
StatusFinaled
Name FIRE SENTRY SYSTEMS
Site Address 400 S BROADWAY AVE
Project NameSt Lukes Tenant Improvements
Customer Number 
ePlanReviewYes
Description
Complete TI of all floors of Washington Group Plaza 1 for St Lukes. Associated with building permit BLD15-04191.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/24/20166/27/20166/27/2016APASS
DetailsJim Page
Final fire alarm inspection passed/complete.
INSP-Final Inspection6/17/20166/20/20166/20/2016PPART
DetailsJim Page
Elevator recall/shunt tested, Audio visual devices tested on level 1, items left for inspection: smoke evacuation system and elevator smoke curtains.
INSP-Final Inspection6/16/20166/17/20166/17/2016PCANC
DetailsJim Page
Inspection request will be rescheduled 20June2016 due to medical emergency with the inspector.
INSP-Final Inspection6/8/20166/10/20166/10/2016APART
DetailsJim Page
Alarm inspection for audio visuals complete for level 3, level 2 and basement level. Final items to test/inspect, level one A/V's, smoke evacuation system for all levels, elevator smoke curtians, elevator recall and elevator shunt
INSP-Alarm Testing6/1/20166/2/20166/2/2016ADONE
DetailsJim Page
Alarm inspection/testing for level 4 complete, contractor had some A/V devices on 3rd floor disconnected (northeast corner class room, total of 4 A/V's), will need to perform inspection for disconnected devices when level 2 is inspected.
INSP-Final Inspection5/19/20165/20/20165/20/2016APART
DetailsJim Page
Project is being inspected in phases, todays inspection consisted of tamper and waterflow switches for penthouse sprinklers, 6th floor sprinklers and 5th floor sprinklers, all devices operated correctly. Audio/Visual devices tested for 6th floor and 5th floor, all AV's operated correctly. Contractor will schedule inspections for other floors when they are ready.
CHANGE STATUS TO (ISS)  5/19/2016 DONE
DetailsChristina Prado
Miscellaneous action  4/27/2016 DONE
Received corrections.
Alarm Plan Check4/27/2016 4/27/2016 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  4/27/2016 DONE
Plan Modification approved with no additional review comments.
Miscellaneous action  4/22/2016 DONE
Emaile Damie to let him know his calculations were not accurate. Requested he make corrections and send them to me.
Plan resubmittals received  4/21/2016 DONE
Plan Modification received
Miscellaneous action  4/13/2016 DONE
Earl Lasiter emaile to indicate floor plan changes that will change the design of the system. He requested the project workflow be opened.
Permit Ready to Issue  3/21/2016 DONE
Issue and Print Permit  3/21/2016 DONE
Inspection Record Card- Fire3/21/2016 3/21/2016 DONE
DetailsCandy A. Nichols
Alarm Plan Check3/18/2016 3/18/2016 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  3/18/2016 DONE
4th submittal approved with review comments and requirements.
Plan resubmittals received  3/17/2016 DONE
Alarm Plan Check3/16/2016 3/16/2016 FAIL
DetailsLee G Meredith
Emiled correction requirements to Earl.
Miscellaneous action  3/15/2016 DONE
Earl emailed additional information about the smoke control system. I responded to say the new material appeared adequate and that note references 3 & 4 are shown on the smoke control graphical operation matrix drawing that need to be addressed. submittal is being returned to add the additional information noted above and details of notes 3 & 4. Earl wanted to know if the electricians could start pulling wire. I informed him that current policy says a permit is required first.
Miscellaneous action  3/14/2016 DONE
Emailed Damie regarding the smoke control panel information that was supplied with this re-submittal. Informed him that more detail is needed for sequence of operation with switches, lights and light colors.
Plan resubmittals received  3/8/2016 DONE
Meeting  3/1/2016 DONE
Earl Lasiter & Josh Bess meeting at PDS with me to discuss the smoke control portion of the project. 9:00 am. Discussed design requirements. Drawings and design need to cover all aspects of the design and be approved by CTA prior to next PDS submittal. U.L. listing requirements. All equipment is to be U.L. listed. Non U.L. will not be allowed. Earl wanted to substitute some smoke detectors from some the smoke control panel to the fire alarm panel. I informed him that the engineer of record could answer this and that all would have to be listed for the use. New drawings are to be submitted to CTA for approval then resubmitted to PDS for premit review.
Alarm Plan Check2/29/2016 2/29/2016 FAIL
DetailsLee G Meredith
2nd review. See review comments dated 2-29-16.
Miscellaneous action  2/29/2016 DONE
2nd review comments emailed to Damie.
Miscellaneous action  2/29/2016 DONE
Received an email from Earl indicating his desire to use a PC driven display as a replacement for the existing one. He will verify U>L> listing of current annunciator today. I suggested again that we get together to discuss the project in detail since design concept is not complete or fully understood by me and review comments have not been properly addressed through the current resubmittal.
Miscellaneous action  2/29/2016 DONE
Earl emailed to indicate an in person meeting would be helpful. He suggested 3-1-16 at 9:00 am.
Miscellaneous action  2/25/2016 DONE
Resubmittal received. Smoke control was not included so submittal was failed. Email sent to Damie informing him that smoke control system needed complete submittal within this permit application before review can continue.
Alarm Plan Check2/25/2016 2/25/2016 FAIL
DetailsLee G Meredith
Resubmittal did not include smoke control design & documents as noted in the 1st review comments.
Miscellaneous action  2/25/2016 DONE
Received an email from Damie as an effort to explain his design. Several issues are still missing or in error, in my opinion. I responded with a suggestion that we get together to discuss the project in detail in an effort to issue approved drawings that meet code requirements and fully detail the work that is being performed.
1st review completed  2/19/2016 FAIL
See 1st fire alarm review comments.
Miscellaneous action  2/19/2016 DONE
Emailed Damie 1st review comments.
Miscellaneous action  2/18/2016 DONE
Confirmed with Damie that Fire Sentry will be executing the smoke control scope of work by contracting that work to State Fire.
Plan assigned to (Lee)2/18/2016 2/18/2016 DONE
DetailsLee G Meredith
Application received  2/16/2016 DONE
Application submitted via PDS Online on Feb 16 2016 11:50AM
Telephone call  2/16/2016  
Damie called to say he needs to upload a corrected drawing and requested the upload task be reopened.
Miscellaneous action  2/16/2016 DONE
Emailed Damie to let him know that multiple drawings are not allowd to be uploaded as a single file. Prescreen review failed again.
Miscellaneous action  2/16/2016 DONE
Damie requested a restart of the work flow for a 3rd time, as he accidentally closed it prior to uploading most recent corrections.