Information based on query as of Sunday, June 30, 2024.
Permit Information
Permit NumberFIR16-00100
StatusFinaled
Name VIKING AUTOMATIC SPRINKLER CO
Site Address 465 W GOWEN RD
Project NameBoise School Dist. Storage Bld
Customer Number 
ePlanReviewYes
Description
Install a new Dry Pipe sprinkler system throughout the new structure. Install new Dry Valve complete with air compressor and FDC located on the wall of the riser room.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/14/201612/15/201612/15/2016APASS
DetailsJim Page
Final fire sprinkler inspection passed/complete
INSP-Sprinkler Rough-in/Hydro9/27/20169/29/20169/29/2016PPASS
DetailsJim Page
24 hour air test for dry system complete.
INSP-Sprinkler Rough-in/Hydro9/27/20169/28/20169/28/2016APART
DetailsJim Page
200 psi hydrostatic test for overhead fire sprinkler piping complete. Rough in inspection for overhead fire sprinkler piping complete. 24 hour air test started at 11:00AM 28SEPT2016 with 40psi on gauge.
Intake Approval  2/22/2016 PASS
Plan assigned to (Tim)2/22/2016 2/22/2016 DONE
DetailsTim Frost
Sprinkler Plan Check2/22/2016 2/22/2016 PASS
DetailsTim Frost
Please, see attached comments.
1st review completed  2/22/2016 PASS
DetailsTim Frost
PLANS/APPL TAKEN TO FRONT DESK  2/22/2016 DONE
DetailsTim Frost
Permit Ready to Issue  2/22/2016 DONE
Issue and Print Permit  2/22/2016 DONE
Inspection Record Card- Fire2/22/2016 2/22/2016 DONE
DetailsChristina Prado
Application received  2/16/2016 DONE
Application submitted via PDS Online on Feb 16 2016 1:54PM