Permit Information
Permit NumberFIR16-00128
StatusIssued
Name WEBSTER FIRE PROTECTION
Site Address 777 W MAIN ST
Project NameCity Center Plaza District TI
Customer Number 
ePlanReviewYes
Description
City Center Plaza District TI to add a new fire alarm system to a new building. Actual address 195 S. Capital Blvd. Associated with building permit BLD15-02494.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/10/201611/10/201611/10/2016PPASS
DetailsTroy Cobbley
Tested functionality and reporting to panel. Engineered electrical plan sheet fire alarm design (special systems) onsite. Fire Alarm shop drawings need to be turned in by fire alarm contractor indentifying passagway notification, via as-built submittal.
INSP-Alarm Testing11/9/201611/9/201611/9/2016PPART
DetailsTroy Cobbley
Inspection and testing complete in commercial kitchen area of level 1a of GBAD.
Miscellaneous action  10/28/2016 DONE
Emailed Ken a copy of the approved alternate that requires notification in the breezeway between the district and Grove Hotel. Originally sent mid March of this year.
INSP-Final Inspection9/1/20169/1/20169/1/2016APART
DetailsJim Page
Final fire alarm inspection for level 4 fire of city center side of the building complete, level 4 of the convention center side of fire alarm system will be completed at a later date.
INSP-Final Inspection8/1/20168/3/20168/3/2016PCANC
DetailsJim Page
Inspection request was for clearwater TI, this inspection request cancelled.
Telephone call  6/15/2016 DONE
Ken called to indicate he found that an additional sprinkler riser existed that he was not aware of during initial submittal. I informed him that changes of that size will require a plan mod and need to be submitted for review.
Plan resubmittals received  3/16/2016 DONE
Alarm Plan Check3/16/2016 3/16/2016 PASS
DetailsLee G Meredith
Third review approved with review comments.
PLANS TAKEN FRONT DESK ALARM  3/16/2016 DONE
thrd submittal approved with review comments and requirements.
Permit Ready to Issue  3/16/2016 DONE
Issue and Print Permit  3/16/2016 DONE
Inspection Record Card- Fire3/16/2016 3/16/2016 DONE
DetailsChristina Prado
Telephone call  3/11/2016 DONE
Ken called regarding review #2 comments. He was sure that the 5th floor service corridor of the ballroom was open to the floor below and that the approved archtectural drawings were in error. I asked him to confirm this with the archtect and resubmit based on the results of that discussion. Also informed him that he needs to review and comply with the approved alternate for the walkway requirements for added weatherproof notification (BLD14-03207). Emailed him a copy of the approved alternate.
Alarm Plan Check3/9/2016 3/9/2016 FAIL
DetailsLee G Meredith
See 2nd review comments.
Miscellaneous action  3/9/2016 DONE
Emailed 2nd review comments to Ken Webster.
Plan resubmittals received  3/8/2016 DONE
Plan assigned to (Lee)3/7/2016 3/7/2016 DONE
DetailsLee G Meredith
1st review completed  3/7/2016 FAIL
Visible notification inadequate.
Miscellaneous action  3/7/2016 DONE
Emailed Ken a copy of the review comments.
Application received  2/26/2016 DONE
Application submitted via PDS Online on Feb 26 2016 11:24AM