INSP-Final Inspection | 6/13/2016 | 6/14/2016 | 6/14/2016 | P | PASS |
Jim Page
|
|
|
Final underground supply inspection passed/complete
|
INSP-Final Inspection | 6/13/2016 | 6/14/2016 | 6/13/2016 | A | CANC |
Jim Page
|
|
|
Please call Jake when you are heading out, thanks! Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello Inspection cancelled from web by: Anthony Minichiello
|
INSP-Supply line flush | 4/5/2016 | 4/6/2016 | 4/6/2016 | A | DONE |
Jim Page
|
|
|
Underground main line flush complete
|
INSP-Supply line flush | 3/18/2016 | 3/18/2016 | 3/18/2016 | A | PASS |
Jim Page
|
|
|
Rough to cover inspection complete for the underground supply, underground approved for cover. Underground hydrostatic test (200 psi for 2 hours) passed/complete
|
Permit Ready to Issue | | | 3/3/2016 | | DONE |
|
|
|
|
Issue and Print Permit | | | 3/3/2016 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 3/3/2016 | | 3/3/2016 | | DONE |
Christina Prado
|
|
|
|
Intake Approval | | | 3/2/2016 | | PASS |
|
|
|
|
Plan assigned to (Tim) | 3/2/2016 | | 3/2/2016 | | DONE |
Tim Frost
|
|
|
|
Sprinkler Plan Check | 3/2/2016 | | 3/2/2016 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
|
1st review completed | | | 3/2/2016 | | PASS |
Tim Frost
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/2/2016 | | DONE |
Tim Frost
|
|
|
|
Application received | | | 3/1/2016 | | DONE |
|
|
|
Application submitted via PDS Online on Mar 1 2016 11:34AM
|