INSP-Final Inspection | 7/26/2016 | 7/27/2016 | 7/27/2016 | A | PASS |
Jim Page
|
|
|
Final fire alarm inspection passed/complete
|
INSP-Final Inspection | 6/13/2016 | 6/14/2016 | 6/14/2016 | P | PART |
Jim Page
|
|
|
Fire alarm inspection partially complete, tested/inspected waterflow, tampers, smoke detector above fire panel and pull station, HVAC units are over 2000cfm so HVAC untis require duct detectors with unit shutdown, HVAC units do not have power connected so duct detectors were INOP at time of inspection. Duct detectors need to be in operation or general contractor needs to have documentation from the city supporting the duct detectors being INOP.
|
Alarm Plan Check | 3/8/2016 | | 3/8/2016 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 3/8/2016 | | DONE |
|
|
|
Plans approved with review comments.
|
Permit Ready to Issue | | | 3/8/2016 | | DONE |
|
|
|
|
Issue and Print Permit | | | 3/8/2016 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 3/8/2016 | | 3/8/2016 | | DONE |
Christina Prado
|
|
|
|
Plan resubmittals received | | | 3/7/2016 | | DONE |
|
|
|
|
Plan assigned to (Lee) | 3/2/2016 | | 3/2/2016 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 3/2/2016 | | FAIL |
|
|
|
Failed pre-sereen review. Review comments sent to Damie for corrections.
|
Application received | | | 3/1/2016 | | DONE |
|
|
|
Application submitted via PDS Online on Mar 1 2016 12:20PM
|