INSP-Final Inspection | 6/21/2016 | 6/22/2016 | 6/22/2016 | A | PASS |
Jim Page
|
|
|
Final fire alarm inspection passed/complete
|
Telephone call | | | 3/18/2016 | | DONE |
|
|
|
Jason called to inform me that the hearing testing has an anechoic room for hearing tests that, per the manufacturer, is not allowed to have foriegn items like horns or strobes installed inside or the warranty and functionality wil be voided. I told Jason that as long as hearing test are administered by an instructor, the notification can be installed in the observation room and not in the testing room. As built drawings will be required. Resubmittal not required.
|
Permit Ready to Issue | | | 3/16/2016 | | DONE |
|
|
|
|
Issue and Print Permit | | | 3/16/2016 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 3/16/2016 | | 3/16/2016 | | DONE |
Christina Prado
|
|
|
|
Plan resubmittals received | | | 3/7/2016 | | DONE |
|
|
|
Corrections uploaded.
|
1st review completed | | | 3/7/2016 | | PASS |
|
|
|
|
Alarm Plan Check | 3/7/2016 | | 3/7/2016 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 3/7/2016 | | DONE |
|
|
|
Plans approved with review comments.
|
Plan assigned to (Lee) | 3/4/2016 | | 3/4/2016 | | DONE |
Lee G Meredith
|
|
|
|
Miscellaneous action | | | 3/4/2016 | | DONE |
|
|
|
Emailed Jason regarding expired attic heat detectors. He said they would replace them. Initially he provided product data that showed fixed and rate of rise detectors. Informed him that rate of rise would not be allowed. He agreed. Found items missing from the legend that need to be properly identified. Sent back on pre-screen review for corrections.
|
Application received | | | 3/3/2016 | | DONE |
|
|
|
Application submitted via PDS Online on Mar 3 2016 10:23AM
|