INSP-Final Inspection | 8/18/2016 | 8/18/2016 | 8/18/2016 | P | PASS |
Jim Page
|
|
|
Previously noted items have been repaired, final fire alarm inspection passed/complete.
|
INSP-Final Inspection | 6/21/2016 | 6/22/2016 | 6/22/2016 | A | FAIL |
Katie Marron
|
|
|
The smoke detectors and strobes on 2nd floor verified "OK". Duct detectors did not shut down fan. Following items needed: - Updated map of devices at panel - Junction box cover by relays in mech room - Retest of duct detectors to verify fan shut down
|
Application received | | | 3/15/2016 | | DONE |
|
|
|
Application submitted via PDS Online on Mar 15 2016 12:35PM
|
Plan assigned to (Lee) | 3/15/2016 | | 3/15/2016 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 3/15/2016 | | PASS |
|
|
|
|
Alarm Plan Check | 3/15/2016 | | 3/15/2016 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 3/15/2016 | | DONE |
|
|
|
Plans approved with review comments.
|
Permit Ready to Issue | | | 3/15/2016 | | DONE |
|
|
|
|
Issue and Print Permit | | | 3/15/2016 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 3/15/2016 | | 3/15/2016 | | DONE |
Christina Prado
|
|
|
|