Permit NumberFIR16-00185
StatusFinaled
Name FIRE SENTRY SYSTEMS
Site Address 715 S CAPITOL BLVD
Project NameBoise Main Library - HVAC upgr
Customer Number 
ePlanReviewYes
Description
2nd Floor HVAC upgrade at main Boise Public Library. Fire alarm systemd changes are to include new smoke detectors, smoke duct detectors and notification. Associated with building permit BLD15-04544.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/18/20168/18/20168/18/2016PPASS
DetailsJim Page
Previously noted items have been repaired, final fire alarm inspection passed/complete.
INSP-Final Inspection6/21/20166/22/20166/22/2016AFAIL
DetailsKatie Marron
The smoke detectors and strobes on 2nd floor verified "OK". Duct detectors did not shut down fan. Following items needed:
- Updated map of devices at panel
- Junction box cover by relays in mech room
- Retest of duct detectors to verify fan shut down
Application received  3/15/2016 DONE
Application submitted via PDS Online on Mar 15 2016 12:35PM
Plan assigned to (Lee)3/15/2016 3/15/2016 DONE
DetailsLee G Meredith
1st review completed  3/15/2016 PASS
Alarm Plan Check3/15/2016 3/15/2016 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  3/15/2016 DONE
Plans approved with review comments.
Permit Ready to Issue  3/15/2016 DONE
Issue and Print Permit  3/15/2016 DONE
Inspection Record Card- Fire3/15/2016 3/15/2016 DONE
DetailsChristina Prado