Permit Information
Permit NumberFIR16-00211
StatusFinaled
Name NORTHWEST FIRE AND SECURITY
Site Address 515 W IDAHO ST
Project NamePaulsen Building
Customer Number 
ePlanReviewYes
Description
New Fire Alarm panel for Sprinkler & HVAC Monitoring. Associated with building permit BLD15-01919.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/17/20168/17/20168/17/2016PPASS
DetailsTroy Cobbley
permit finaled
INSP-Sprinkler Rough-in/Hydro8/17/20168/17/20168/17/2016PCANC
DetailsTroy Cobbley
Wrong inspection type scheduled
INSP-Sprinkler Rough-in/Hydro8/16/20168/17/20168/17/2016PCANC
DetailsTroy Cobbley
Wrong inspection type scheduled
INSP-Final Inspection8/15/20168/16/20168/16/2016PFAIL
DetailsTroy Cobbley
Need approved drawings addressing the wireless dialer instead of two phone lines, need document box, need map at facp, need to test the duct smoke detectors, need nfpa 72s
Miscellaneous action  8/16/2016 DONE
As built drawings received from Rick Groom. Uploaded into approved folder in projectdox.
Meeting  7/6/2016 DONE
Met Rick on site to review panel location in the lobby. The panel is rather large so the owner is looking for acceptable placement options. I told Rick that it could be installed just inside the west hall of the 1st floor. This will be a bit more astecially pleasing but still obvious to responders. His other option is to install a remote annunciator in the lobby and relocated the fire alarm out of site. Any changes will require as built drawings.
Meeting  5/4/2016 DONE
Rick Groom came to the office to discuss the placement of the fire alarm panel in the lobby. He showed pictures that implied the fire alarm panel location may have to change due to lack of wall space. We agreed that if the panel needed to be relocated outside of the vicinity of the lobby / entry area that a remote annunciator would need to be added.
Permit Ready to Issue  4/8/2016 DONE
Issue and Print Permit  4/8/2016 DONE
Inspection Record Card- Fire4/8/2016 4/8/2016 DONE
DetailsChristina Prado
Application received  3/22/2016 DONE
Application submitted via PDS Online on Mar 22 2016 2:09PM
Plan assigned to (Lee)3/22/2016 3/22/2016 DONE
DetailsLee G Meredith
1st review completed  3/22/2016 PASS
Alarm Plan Check3/22/2016 3/22/2016 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  3/22/2016 DONE
Plans approved with review comments.