INSP-Final Inspection | 8/17/2016 | 8/17/2016 | 8/17/2016 | P | PASS |
Troy Cobbley
|
|
|
permit finaled
|
INSP-Sprinkler Rough-in/Hydro | 8/17/2016 | 8/17/2016 | 8/17/2016 | P | CANC |
Troy Cobbley
|
|
|
Wrong inspection type scheduled
|
INSP-Sprinkler Rough-in/Hydro | 8/16/2016 | 8/17/2016 | 8/17/2016 | P | CANC |
Troy Cobbley
|
|
|
Wrong inspection type scheduled
|
INSP-Final Inspection | 8/15/2016 | 8/16/2016 | 8/16/2016 | P | FAIL |
Troy Cobbley
|
|
|
Need approved drawings addressing the wireless dialer instead of two phone lines, need document box, need map at facp, need to test the duct smoke detectors, need nfpa 72s
|
Miscellaneous action | | | 8/16/2016 | | DONE |
|
|
|
As built drawings received from Rick Groom. Uploaded into approved folder in projectdox.
|
Meeting | | | 7/6/2016 | | DONE |
|
|
|
Met Rick on site to review panel location in the lobby. The panel is rather large so the owner is looking for acceptable placement options. I told Rick that it could be installed just inside the west hall of the 1st floor. This will be a bit more astecially pleasing but still obvious to responders. His other option is to install a remote annunciator in the lobby and relocated the fire alarm out of site. Any changes will require as built drawings.
|
Meeting | | | 5/4/2016 | | DONE |
|
|
|
Rick Groom came to the office to discuss the placement of the fire alarm panel in the lobby. He showed pictures that implied the fire alarm panel location may have to change due to lack of wall space. We agreed that if the panel needed to be relocated outside of the vicinity of the lobby / entry area that a remote annunciator would need to be added.
|
Permit Ready to Issue | | | 4/8/2016 | | DONE |
|
|
|
|
Issue and Print Permit | | | 4/8/2016 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 4/8/2016 | | 4/8/2016 | | DONE |
Christina Prado
|
|
|
|
Application received | | | 3/22/2016 | | DONE |
|
|
|
Application submitted via PDS Online on Mar 22 2016 2:09PM
|
Plan assigned to (Lee) | 3/22/2016 | | 3/22/2016 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 3/22/2016 | | PASS |
|
|
|
|
Alarm Plan Check | 3/22/2016 | | 3/22/2016 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 3/22/2016 | | DONE |
|
|
|
Plans approved with review comments.
|