INSP-Final Inspection | 8/22/2016 | 8/24/2016 | 8/24/2016 | A | PASS |
Jim Page
|
|
|
Final inspection for dry standpipe complete, knox caps are on order and will be installed when received. Hose valve caps will be installed towards the end of the apartment complex completion to prevent theft of the brass.
|
INSP-Sprinkler Rough-in/Hydro | 4/18/2016 | 4/21/2016 | 4/21/2016 | P | PASS |
Jim Page
|
|
|
Rough in inspection for building standpipe complete. 200 psi hydrostatic test for building standpipe complete.
|
Miscellaneous action | | | 4/14/2016 | | DONE |
|
|
|
The FD is ok with dry standpipes but required
Locking KNOX FDC caps
One FDC connection for the standpipes and system.
I knew the code section was in NFPA 14 but since IFC overrules and it was not mention in IFC. Well I just wanted to make sure.
The IFC comment could always be made to happen. (Make them supply a heated chase and or heat tracing.) That is what I meant by huge expense.
It is going to be difficult to tie the FDC together. The regular FDC is at the side of the building. The SP FDC is in the middle. However, anything is possible. I will call them and see how much blow back I get.
In retrospect, I should have been more thorough on my question to you. Sorry.
Cordially,
Tim Frost, S.E.T.
Tim Frost, S.E.T.
Fire Sprinkler Plans Examiner
Planning & Development Services
Phone: ###-####
E-Mail: tfrost@cityofboise.org
150 North Capitol Boulevard
Boise, ID. 83701
From: Ronald Johnson
Sent: Wednesday, March 23, 2016 3:37 PM
To: Tim Frost
Subject: RE: Kensington
Tim,
First a couple code sections.
905.8 Dry standpipes. Dry standpipes shall not be installed.
Exception: Where subject to freezing and in accordance
with NFPA 14.
NFPA 14
5.4.1.1* Class I standpipe systems shall be permitted to be automatic
dry, automatic wet, semiautomatic dry, manual dry, or
manual wet in buildings not classified as high-rise buildings.
I just talked to Romeo about this to see how he’s handled it before. He hasn’t come across this exact scenario, nor have I. We are ok with the concept with the addition of a couple items.
1. Locking Knox caps on FDC’s.
2. Shared FDC with sprinklers to prevent us from having to supply an FDC and a standpipe connection.
Do you think that is doable?
Thanks,
Ron Johnson
Division Chief – Assistant Fire Marshal
###-#### -Office
###-#### -Cell
rjohnson@cityofboise.org
333 N. Mark Stall Place
Boise, ID 83704
From: Tim Frost
Sent: Wednesday, March 23, 2016 1:47 PM
To: Ronald Johnson
Subject: Kensington
We have talked several times about this project. However, just to make sure, you are ok with dry manual standpipes in these NPFA 13R apartment buildings; correct? They are not specifically referenced in IFC. The only reference for dry manual appears to be parking garages and basement. There really is any better way of doing them without a huge exspense.
905.3 Required Installations.
Standpipe systems shall be installed where required by Sections 905.3.1 through 905.3.8. Standpipe systems are allowed to be combined with automatic sprinkler
systems.
Exception: Standpipe systems are not required in Group R-3 occupancies.
905.3.1 Height.
Class III standpipe systems shall be installed throughout buildings where the floor level of the highest story is located more than 30 feet (9144 mm) above the
lowest level of the fire department vehicle access, or where the floor level of the lowest story is located more than 30 feet (9144 mm) below the highest level of
fire department vehicle access.
Exceptions:
1. Class I standpipes are allowed in buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or
903.3.1.2.
2. Class I manual standpipes are allowed in open parking garages where the highest floor is located not more than 150 feet (45 720 mm) above the
lowest level of fire department vehicle access.
3. Class I manual dry standpipes are allowed in open parking garages that are subject to freezing temperatures, provided that the hose connections are
located as required for Class II standpipes in accordance with Section 905.5.
4. Class I standpipes are allowed in basements equipped throughout with an automatic sprinkler system.
5. In determining the lowest level of fire department vehicle access, it shall not be required to consider:
5.1. Recessed loading docks for four vehicles or less, and
5.2. Conditions where topography makes access from the fire
|
Intake Approval | | | 4/11/2016 | | PASS |
|
|
|
|
Plan assigned to (Tim) | 4/11/2016 | | 4/11/2016 | | DONE |
Tim Frost
|
|
|
|
Sprinkler Plan Check | 4/11/2016 | | 4/11/2016 | | FAIL |
Tim Frost
|
|
|
|
1st review completed | | | 4/11/2016 | | FAIL |
|
|
|
|
Miscellaneous action | | | 4/11/2016 | | DONE |
Tim Frost
|
|
|
Emailed contractor in regards to failed review.
|
Sprinkler Plan Check | 4/11/2016 | | 4/11/2016 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 4/11/2016 | | DONE |
Tim Frost
|
|
|
|
Permit Ready to Issue | | | 4/11/2016 | | DONE |
|
|
|
|
Issue and Print Permit | | | 4/11/2016 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 4/11/2016 | | 4/11/2016 | | DONE |
Brittany Hill
|
|
|
|
Application received | | | 3/23/2016 | | DONE |
|
|
|
Application submitted via PDS Online on Mar 23 2016 4:51PM
|