INSP-Final Inspection | 9/14/2016 | 9/15/2016 | 9/15/2016 | P | PASS |
Jim Page
|
|
|
Final fire sprinkler inspection passed/complete.
|
INSP-Sprinkler Rough-in/Hydro | 8/3/2016 | 8/3/2016 | 8/3/2016 | A | PASS |
Jim Page
|
|
|
24 hour air test for new dry system install passed/complete.
|
INSP-Sprinkler Rough-in/Hydro | 8/1/2016 | 8/2/2016 | 8/2/2016 | A | PART |
Jim Page
|
|
|
200 psi hydrostatic test complete, 24 hour air test started at 12:00 pm @ 40psi
|
INSP-Sprinkler Rough-in | 8/1/2016 | 8/1/2016 | 8/1/2016 | P | PASS |
Jim Page
|
|
|
Rough to cover inspection for overhead fire sprinkler piping located above ceiling grid area's complete, approved for cover.
|
INSP-Sprinkler Rough-in/Hydro | 5/6/2016 | 5/6/2016 | 5/6/2016 | P | PASS |
Jim Page
|
|
|
Hydrostatic test complete for overhead wet system in northeast 50 degree cooler, hydrostatic test complete for dry system located northwest 38 degree cooler.
|
Permit Ready to Issue | | | 4/18/2016 | | DONE |
|
|
|
|
Issue and Print Permit | | | 4/18/2016 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 4/18/2016 | | 4/18/2016 | | DONE |
Candy A. Nichols
|
|
|
|
Sprinkler Plan Check | 4/15/2016 | | 4/15/2016 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 4/15/2016 | | DONE |
Tim Frost
|
|
|
|
Sprinkler Plan Check | 4/8/2016 | | 4/8/2016 | | FAIL |
Tim Frost
|
|
|
|
1st review completed | | | 4/8/2016 | | FAIL |
Tim Frost
|
|
|
|
Miscellaneous action | | | 4/8/2016 | | DONE |
Tim Frost
|
|
|
Emailed contractor in regards to failed review.
|
Intake Approval | | | 4/5/2016 | | PASS |
|
|
|
|
Plan assigned to (Tim) | 4/5/2016 | | 4/5/2016 | | DONE |
Tim Frost
|
|
|
|
Application received | | | 3/28/2016 | | DONE |
|
|
|
Application submitted via PDS Online on Mar 28 2016 3:13PM
|