Permit Information
Permit NumberFIR16-00324
StatusFinaled
Name TRIBAL FIRE SYSTEMS
Site Address 7000 W VICTORY RD
Project NameCritical systems, Inc TI
Customer Number 
ePlanReviewYes
Description
[Critical Systems, Inc - TI]
Add sprinklers to new work room

(CRITICAL SYSTEMS, Inc – Phase I – Two story enclosed area inside warehouse) Permit is to create the structural shell of a new 4,935 square foot two story area inside the existing warehouse. Note: this permit will change construction type to a VB building from a IIB building and change warehouse from an S-1 occupancy to an S-2 occupancy. Although the 2nd floor will eventually add area at this time it is unoccupied with no stairs to access the area; therefore, this permit does not increase the area of the building. The existing building is 37,762 square feet. This building is fire sprinklered for building area and fire area. Approval contingent upon adhering to the approved plans on file and attached engineering. Work to include: new isolated concrete footings, new steel columns / beams, new wood bearing walls, new i-joist floors, and new rough openings. This building is fully Fire Sprinklered with an approved Fire Alarm system. New construction will require the sprinkler system be extended to cover this area immediately in order to maintain coverage. **TLW**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/10/20166/10/20166/10/2016PPASS
DetailsTroy Cobbley
Permit finaled. Overhead hydro test passed
INSP-Final Inspection6/8/20166/9/20166/9/2016PCANC
DetailsTroy Cobbley
To be rescheduled for tomorrow morning for a hydro.
INSP-Sprinkler Rough-in/Hydro6/8/20166/9/20166/9/2016APART
DetailsTroy Cobbley
General rough-in passed. Earth quake bracing has not been installed yet. Need more supply pipe installed prior to hydro test. Need as-builts showing the four additional heads installed on kick backs on the west end of the system. The combustible concealed spaces/double walls will need to be addressed prior to a cover inspection.
Permit Ready to Issue  5/31/2016 DONE
all requirments met
Issue and Print Permit  5/31/2016 DONE
Inspection Record Card- Fire5/31/2016 5/31/2016 DONE
DetailsCarlos Velazquez
Sprinkler Plan Check5/27/2016 5/27/2016 PASS
DetailsTim Frost
Please, see attached comments.
PLANS/APPL TAKEN TO FRONT DESK  5/27/2016 DONE
DetailsTim Frost
Intake Approval  5/23/2016 PASS
Plan assigned to (Tim)5/23/2016 5/23/2016 DONE
DetailsTim Frost
Sprinkler Plan Check5/23/2016 5/23/2016 FAIL
DetailsTim Frost
1st review completed  5/23/2016 FAIL
DetailsTim Frost
Miscellaneous action  5/23/2016 DONE
DetailsTim Frost
Emailed contractor in regards to failed review.
Application received  5/11/2016 DONE
Application submitted via PDS Online on May 11 2016 8:51AM