Permit Information
Permit NumberFIR16-00336
StatusFinaled
Name ALL VALLEY FIRE
Site Address 1403 N PROMONTORY RD
Project NameSkoro Residence
Customer Number 
ePlanReviewYes
Description
[Skoro Residence]
The fire sprinkler scope of work consists of protecting a two level residence with a partial basement per NFPA 13D

The underground piping is under permit FIR16-00036

WUI ZONE A Permit for the construction of a new 8,091 sq. ft., two story with a basement (first story 4,573 sq. ft., second story 2,2552 sq. ft., basement level 966 sq. ft.) single family dwelling with 3 bedrooms, 5 bathrooms, approximately 643 sq. ft. of covered patio/porch and a 1,828 sq. ft. attached garage per the approved plans, plan review report and any notations. R-1C zoning and setbacks per planning. LEG
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/18/20181/19/20181/19/2018PPASS
DetailsJim Page
Final fire sprinkler inspection complete.
INSP-Sprinkler Rough-in11/16/201611/17/201611/17/2016APASS
DetailsJim Page
Previously noted items have been repaired in regards to the pipe tenting, documentation had not been received for the foam type insulation at time of inspection, overhead fire sprinkler piping will be approved for cover, if documentation does not support compatability with CPVC then a necessary repair/replacement of piping will be required. Overhead fire sprinkler piping approved for cover at general contractors discretion.
INSP-Sprinkler Rough-in11/15/201611/15/201611/15/2016PFAIL
DetailsTroy Cobbley
I pointed out several locations where tenting needed modified which included in the Master Bedroom and a vertical piece of pipe on the second floor above the Master Bedroom. Also a letter is needed that states the spray on foam insulation is compatible with the cpvc piping. I noted that the spray on foam has been sprayed behind as well as on top fo the piping. The building contractor, Bob, stated that there is adequate insulation behind the piping and the foam on the interior side of the piping is not detrimental to heat transfer. Another cover inspection is needed with the above corrections prior to covering the piping.
INSP-Sprinkler Rough-in10/13/201610/14/201610/14/2016APART
DetailsJim Page
Rough to cover inspection for overhead fire sprinkler piping complete, overhead fire sprinkler piping located between levels approved for cover, fire sprinkler piping located in attic spaces cannot be covered until tenting insualtion is installed.
Sprinkler Plan Check6/17/2016 6/17/2016 PASS
DetailsTim Frost
Please, see attached comments.
PLANS/APPL TAKEN TO FRONT DESK  6/17/2016 DONE
DetailsTim Frost
Permit Ready to Issue  6/17/2016 DONE
all requirments met
Issue and Print Permit  6/17/2016 DONE
Inspection Record Card- Fire6/17/2016 6/17/2016 DONE
DetailsCarlos Velazquez
Intake Approval  6/15/2016 PASS
Plan assigned to (Tim)6/15/2016 6/15/2016 DONE
DetailsTim Frost
Sprinkler Plan Check6/15/2016 6/15/2016 FAIL
DetailsTim Frost
1st review completed  6/15/2016 FAIL
DetailsTim Frost
Miscellaneous action  6/15/2016 DONE
DetailsTim Frost
Emailed contractor in regards to failed review.
Application received  5/16/2016 DONE
Application submitted via PDS Online on May 16 2016 12:26PM