Permit Information
Permit NumberFIR16-00357
StatusFinaled
Name SIMPLEX GRINNELL
Site Address 1055 N CURTIS RD
Project NameSARMC Easy Street Remodel
Customer Number 
ePlanReviewYes
Description
Easy Street Remodel SARM 4th Floor scope is to modify existing fire alarm system providing new devices, relocate and demo existing. Associated with building permit BLD16-00628.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/11/20178/14/20178/14/2017APASS
DetailsJim Page
Previously noted items have been repaired, final fire alarm inspection for area of work passed/complete.
INSP-Alarm Testing11/16/201611/17/201611/17/2016APART
DetailsTroy Cobbley
New notification devices functioned correctly in the new scope of work. The issues is the new devices do not sync with the existing devices outside of the scope of work. I contacted Ron with the Boise Fire Dept and he stated that the new and old devices will need to sync as per code requirements.
INSP-Alarm Testing10/19/201610/20/201610/20/2016APART
DetailsTroy Cobbley
For a final sign off the new notification devices need to be installed and tested. Per Scott Arellano a 30 temporary for life safety is ok until the new devices are installed and tested.
CHANGE STATUS TO (ISS)  10/17/2016 DONE
Plan Modification Accepted  10/14/2016 DONE
CHANGE STATUS TO (REV)  10/14/2016 DONE
1st review completed  10/14/2016 PASS
Alarm Plan Check10/14/2016 10/14/2016 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  10/14/2016 DONE
Plan modification approved. No additional plan review comments.
INSP-Alarm Testing10/12/201610/13/201610/13/2016ADONE
DetailsTroy Cobbley
Need to add smoke detector in the Nurses Station area, need to relocate two other smoke detectors away from air diffusers, one wall mount strobe was non-functional, audio was not temporal but march time, elevator recall was not tested or any of the new smoke detectors in the corridor system. Scott Arellano is ok with a 30 day temporary to allow time for the contractor to correct the audio as long as all other items have been corrected.
Alarm Plan Check6/13/2016 6/13/2016 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  6/13/2016 DONE
Plan modification approved as noted. No additional review comments.
Permit Ready to Issue  6/13/2016 DONE
Issue and Print Permit  6/13/2016 DONE
Inspection Record Card- Fire6/13/2016 6/13/2016 DONE
DetailsCandy A. Nichols
Miscellaneous action  6/13/2016 DONE
Dante emailed architect's documents that show the bathroom as non functional so weatherproof notification will not be required. The game room also has an area noted as requiring coverage but the furniture layout shows that this is not space that can be occupied so visual notification not needed.
Miscellaneous action  6/9/2016 DONE
Project reopened for plan modification at vendor's request.
CHANGE STATUS TO (REV)  6/9/2016 DONE
Reopened for plan modification
1st review completed  6/1/2016 PASS
Alarm Plan Check6/1/2016 6/1/2016 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  6/1/2016 DONE
Plans approved as noted with review comments.
Permit Ready to Issue  6/1/2016 DONE
all requirments met
Issue and Print Permit  6/1/2016 DONE
Inspection Record Card- Fire6/1/2016 6/1/2016 DONE
DetailsCarlos Velazquez
Application received  5/26/2016 DONE
Application submitted via PDS Online on May 26 2016 10:35AM
Plan assigned to (Lee)5/26/2016 5/26/2016 DONE
DetailsLee G Meredith