INSP-Final Inspection | 8/24/2016 | 8/24/2016 | 8/24/2016 | P | PASS |
Jim Page
|
|
|
Final fire alarm inspection passed/complete.
|
INSP-Final Inspection | 8/5/2016 | 8/5/2016 | 8/5/2016 | P | PART |
Jim Page
|
|
|
Final fire alarm inspection complete, audio visual device in south cooler did not operate, will verify A/V has been repaired during commercial hood suppression inspection.
|
Telephone call | | | 7/29/2016 | | DONE |
|
|
|
Rob confirmed that the dampers previously mentioned were actually control dampers and not smoke dampers. Therefore, detection is not needed.
|
Miscellaneous action | | | 7/21/2016 | | DONE |
|
|
|
Rob Ahten emailed to say that 2 fire smoke dampers with detection have been added to the scope. He wanted to know if this could be documented on as built drawings. I informed him that it could.
|
Telephone call | | | 6/14/2016 | | DONE |
|
|
|
Rob requested the work flow to be reopened for a plan modification of adding a NAC power supply.
|
CHANGE STATUS TO (REV) | | | 6/14/2016 | | DONE |
|
|
|
|
Plan Modification Accepted | | | 6/14/2016 | | DONE |
|
|
|
Plan modification for addition of a NAC power supply, addition of tenant audio system shunt and removal of non required duct detectors.
|
Alarm Plan Check | 6/14/2016 | | 6/14/2016 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 6/14/2016 | | DONE |
|
|
|
Plan mod approved with revise review comments.
|
CHANGE STATUS TO (ISS) | | | 6/14/2016 | | DONE |
|
|
|
|
(F) Reprint permit | | | 6/14/2016 | | DONE |
|
|
|
|
Miscellaneous action | | | 6/3/2016 | | DONE |
|
|
|
Rob Ahted emailed to say that the ahu's shown on the fure alarm submittal drawings are actually fan coil units and don't need duct detection. He wanted to know if we would allow them to be deleted. I informed him that they did not have to put them in but as built drawings would be requried to be sent in at the time of project completion.
|
Permit Ready to Issue | | | 6/2/2016 | | DONE |
|
|
|
|
Issue and Print Permit | | | 6/2/2016 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 6/2/2016 | | 6/2/2016 | | DONE |
Christina Prado
|
|
|
|
Application received | | | 6/1/2016 | | DONE |
|
|
|
Application submitted via PDS Online on Jun 1 2016 11:03AM
|
Plan assigned to (Lee) | 6/1/2016 | | 6/1/2016 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 6/1/2016 | | PASS |
|
|
|
|
Alarm Plan Check | 6/1/2016 | | 6/1/2016 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 6/1/2016 | | DONE |
|
|
|
Plans approved with drawing notes and review comments.
|