Permit Information
Permit NumberFIR16-00383
StatusFinaled
Name SIMPLEX GRINNELL
Site Address 505 W BROAD ST
Project Name5TH & BROAD - SHELL & CORE
Customer Number 
ePlanReviewYes
Description
5th&Broad (The Fowler) core & shell scope of work is to provide and install new automatic and manual Fire Alarm System on a new building. Area of Work covers 5 live/work units, 4 future tenant spaces on the 1st floor, and accessory office/residential amenity rooms on the 2nd floor. Associated with building permit BLD15-03835.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/28/20183/1/20183/1/2018PCANC
DetailsJim Page
Call prior to going Phone #: 2089411846 >> Inspection requested via mobile web by SVC Brian A
INSP-Final Inspection3/1/20183/1/20183/1/2018PPASS
DetailsJim Page
Final fire alarm inspection complete.
INSP-Final Inspection2/28/20182/28/20182/28/2018PCANC
DetailsJim Page
As late as possible Phone #: 2089411846 >> Inspection requested via mobile web by SVC Brian A Inspection cancelled via mobile web on Wednesday, February 28, 2018.
INSP-Alarm Testing2/9/20182/9/20182/9/2018PDONE
DetailsJim Page
Fire alarm testing for levels 3 and 4 complete.
INSP-Alarm Testing1/30/20181/30/20181/30/2018PDONE
DetailsJim Page
Fire alarm testing for stairwell number 2 pressurization complete.
INSP-Alarm Testing1/29/20181/29/20181/29/2018PDONE
DetailsJim Page
Fire alarm testing complete for level 1 lobby and level 2 common areas. Additional notification needed for level 1.5 southside of garage.
INSP-Alarm Testing1/26/20181/26/20181/26/2018PPART
DetailsJim Page
Fire alarm testing for levels 5 and 6 complete.
INSP-Alarm Testing1/23/20181/23/20181/23/2018PDONE
DetailsJim Page
More fire alarm testing needs to happen on level 6 before TCO
INSP-Alarm Testing1/16/20181/16/20181/16/2018PDONE
DetailsJim Page
Fire alarm inspection/testing for level 7 complete.
INSP-Alarm Testing1/9/20181/16/20181/16/2018ACANC
DetailsJim Page
Call prior to going Phone #: 2089411846 >> Inspection requested via mobile web by SVC Brian A Inspection cancelled via mobile web on Tuesday, January 16, 2018.
CHANGE STATUS TO (ISS)  10/10/2017 DONE
(F) Reprint permit  10/10/2017 DONE
Alarm Plan Check10/9/2017 10/9/2017 PASS
DetailsLee G Meredith
Plans approved as noted in the review comments and notes on drawing FA-502.
PLANS TAKEN FRONT DESK ALARM  10/9/2017 DONE
Plan modification approved as noted.
Permit Ready to Issue  10/9/2017 DONE
Plan Modification Accepted  10/6/2017 DONE
Miscellaneous action  10/6/2017 DONE
Emailed John to ask if stairwell fan status lights showed the actual status of the control switches or th actual fans run status. He replied to with a mechanical drawing showing the interface of lights, switches and relaysthat explains most functions.
Miscellaneous action  9/25/2017 DONE
John Haber emailed to ask if smoke detectors are allowed in the garage. I informe him that unless enclosed in a tempered vestibule or room that they are not. Heat detector is required.
INSP-Alarm Testing9/18/20179/20/20179/20/2017APART
DetailsJim Page
Fire alarm testing complete for fire pump riser room/fire pump room dry systems (Parking levels 1 and 2 dry systems). All tampers and flow switches in fire pump room complete, fire pump monitoring complete, tampers and flows complete for levels 1 and 2 wet systems.
Telephone call  9/15/2017 DONE
Dante requested this workflow be reopened for a plan modification.
INSP-Alarm Testing9/14/20179/14/20179/14/2017PDONE
DetailsTroy Cobbley
Today I verified the panel, batteries, phone lines, phone line troubles, battery troubles and smoke detector over the panel. Most other devices have not been connected to the main fire alarm panel. I was unable to test the hood suppression system and a/v's in the Pizza tenant due to the approved plans for the space not being on site. I also pointed out the a plan modification is needed for the new devices (fire pump) and deletion of devices. Also a plan modification is needed for stair shaft pressurization as noted on the city approved fire alarm plans.
Inspection Record Card- Fire6/29/2016 6/29/2016 DONE
DetailsBrittany Hill
(F) Reprint permit  6/29/2016 DONE
1st review completed  6/23/2016 PASS
Alarm Plan Check6/23/2016 6/23/2016 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  6/23/2016 DONE
Plans approved with review comments and noted requirements on the drawings.
Permit Ready to Issue  6/23/2016 DONE
Issue and Print Permit  6/23/2016 DONE
Inspection Record Card- Fire6/23/2016 6/23/2016 DONE
DetailsCandy A. Nichols
Plan assigned to (Lee)6/13/2016 6/13/2016 DONE
DetailsLee G Meredith
Miscellaneous action  6/13/2016 DONE
Informed Dante that an approved design alternate provides for a pressurization fan in stairwell 2 and that it will need to meet the requirements of IFC / IBC section 909. This is not shown on any of the 4 different phase submittals. I emailed him a copy of the approved alternate as a reference. He will go over this with the engineer of record to determine how they want to handle this.
Application received  6/9/2016 DONE
Application submitted via PDS Online on Jun 9 2016 10:55AM