Permit Information
Permit NumberFIR16-00392
StatusFinaled
Name PROTEX
Site Address 8485 W USTICK RD
Project NameBoise Fire Station #4
Customer Number 
ePlanReviewYes
Description
Add code compliant fire alarm system to new construction. Associated with building permit BLD16-01040.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/1/20176/1/20176/1/2017PPASS
DetailsTroy Cobbley
permit finaled. fan has been relocated
INSP-Final Inspection5/30/20175/31/20175/31/2017AFAIL
DetailsTroy Cobbley
All items tested ok except that the fan in the Truck Bay will need to be shut down upon flow of water. Resubmittals or as-builts will be required at the plan reviewers request.
Telephone call  5/31/2017 DONE
Rob called to discuss the requirements of shutdown of the Big Ass circulation fan. I informed him that if the building has sprinklers, the manufacturer has shutdown indicated in the installation manual as a requirement. I emailed a copy of the page that showed the requirement to Rob.
Miscellaneous action  5/31/2017 DONE
Received as built drawing from Rob that showed a control circuit to shut down the fan. Approved.
INSP-Final Inspection5/25/20175/26/20175/26/2017ACANC
DetailsTroy Cobbley
Contact is Sean. Phone #: ###-#### Inspection requested via web by Morgan Ahten
Miscellaneous action  4/18/2017 DONE
Received as built drawing with GSM communicator substituted for original dialer.
Miscellaneous action  7/26/2016 DONE
Rob requested workflow be re-opened due to product change.
Plan Modification Accepted  7/26/2016 DONE
CHANGE STATUS TO (REV)  7/26/2016 DONE
Resubmittal due to product change.
1st review completed  7/26/2016 PASS
Alarm Plan Check7/26/2016 7/26/2016 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  7/26/2016 DONE
Plan modificatio approved. No additional review comments.
CHANGE STATUS TO (ISS)  7/26/2016 DONE
Plan mod. No fees due per Lee M
Plan assigned to (Lee)6/16/2016 6/16/2016 DONE
DetailsLee G Meredith
1st review completed  6/16/2016 PASS
Alarm Plan Check6/16/2016 6/16/2016 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  6/16/2016 DONE
Plans approved with review comments.
Permit Ready to Issue  6/16/2016 DONE
Issue and Print Permit  6/16/2016 DONE
Inspection Record Card- Fire6/16/2016 6/16/2016 DONE
DetailsKristal Soland
Application received  6/15/2016 DONE
Application submitted via PDS Online on Jun 15 2016 11:07AM