INSP-Final Inspection | 8/3/2016 | 8/4/2016 | 8/4/2016 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled. Rand Phone #: ###-####
|
INSP-Final Inspection | 8/3/2016 | 8/3/2016 | 8/4/2016 | P | CANC |
Troy Cobbley
|
|
|
Rand Phone #: ###-####
|
INSP-Final Inspection | 8/2/2016 | 8/2/2016 | 8/2/2016 | P | FAIL |
Jim Page
|
|
|
Final fire alarm inspection performed for new fire alarm panel and associated devices. All audio visual devices tested, tampers and flow from fire sprinkler system reported to fire panel. Tested pull station as well as smoke by FACP. All devices test satisfactorily but did not report out to monitoring service. Alarm signals need to be verfied by monitoring service before FIR permit can be finaled.
|
Permit Ready to Issue | | | 7/5/2016 | | DONE |
|
|
|
|
Issue and Print Permit | | | 7/5/2016 | | DONE |
|
|
|
|
(F) Reprint permit | | | 7/5/2016 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 7/5/2016 | | 7/5/2016 | | DONE |
Candy A. Nichols
|
|
|
|
(F) Reprint permit | | | 7/5/2016 | | DONE |
|
|
|
|
(F) Reprint permit | | | 7/5/2016 | | DONE |
|
|
|
|
Plan assigned to (Lee) | 7/1/2016 | | 7/1/2016 | | FAIL |
Lee G Meredith
|
|
|
|
Miscellaneous action | | | 7/1/2016 | | DONE |
|
|
|
Troy Cobbley called to say the system in the building does not match what is shown on the plans. Numerous existing devices that were to be removed are still existing. Troy discussed the site status and lack of existing permit with Scott. Plans are to be issued with noted requirements and a requirement for as built drawings at completion. Any changes from the approved drawings and notes will require a plan modification submittal.
|
1st review completed | | | 7/1/2016 | | PASS |
|
|
|
As noted on the drawings.
|
Alarm Plan Check | 7/1/2016 | | 7/1/2016 | | PASS |
Lee G Meredith
|
|
|
As noted on the drawings.
|
PLANS TAKEN FRONT DESK ALARM | | | 7/1/2016 | | DONE |
|
|
|
Plans conditionally approved as ntoed in comments and on the drawing.
|
Application received | | | 6/30/2016 | | DONE |
|
|
|
Application submitted via PDS Online on Jun 30 2016 2:46PM
|