INSP-Final Inspection | 7/28/2016 | 7/29/2016 | 7/29/2016 | A | PASS |
Troy Cobbley
|
|
|
permit finaled
|
INSP-Final Inspection | 7/18/2016 | 7/19/2016 | 7/19/2016 | A | FAIL |
Troy Cobbley
|
|
|
Relocate or add strobe as discussed in the bedroom, revise plans to show a horn being installed in the corridor as shown on the approved plans. See note on monitoring in electronic permit activities.
|
Telephone call | | | 7/19/2016 | | DONE |
|
|
|
Per IDAPA 16.03.22_405_02 the fire alarm system is required to be electrically supervised. It is not required to have off site monitoring per the IDAPA rule; however, final approval is up to the Licensing and Survey Agency of the state of Idaho.
|
INSP-Final Inspection | 7/11/2016 | 7/12/2016 | 7/11/2016 | A | CANC |
Troy Cobbley
|
|
|
Phone #: ###-#### >> Inspection requested via web by Sam Ball Inspection cancelled from web by: Sam Ball
|
Plan resubmittals received | | | 7/7/2016 | | DONE |
|
|
|
|
Alarm Plan Check | 7/7/2016 | | 7/7/2016 | | PASS |
Lee G Meredith
|
|
|
Approved as noted. As built drawings, calculations and product data due at completion of project.
|
PLANS TAKEN FRONT DESK ALARM | | | 7/7/2016 | | DONE |
|
|
|
Plans approved as noted. No review comments.
|
Permit Ready to Issue | | | 7/7/2016 | | DONE |
|
|
|
|
Issue and Print Permit | | | 7/7/2016 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 7/7/2016 | | 7/7/2016 | | DONE |
Kristal Soland
|
|
|
|
Plan assigned to (Lee) | 7/5/2016 | | 7/5/2016 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 7/5/2016 | | FAIL |
|
|
|
No scale graph shown on drawings. Unable to verify spacing. Emailed Mary to let her know.
|
Application received | | | 7/4/2016 | | DONE |
|
|
|
Application submitted via PDS Online on Jul 4 2016 6:48AM
|