Permit Information
Permit NumberFIR16-00446
StatusFinaled
Name TASKER ELECTRICAL CONSTRUCTION INC
Site Address 2967 W CRESCENT RIM DR
Project NameCrescent Rim #4
Customer Number 
ePlanReviewYes
Description
Extend the existing FA system into Bldg #4 utilizing a new SLC loop card. Original FA design was from 2008. Associated with building permit BLD06-02324.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/30/201710/31/201710/31/2017APASS
DetailsTroy Cobbley
permit finaled
INSP-Final Inspection10/25/201710/27/201710/27/2017ACANC
DetailsTroy Cobbley
Bob Thorton will be the site contact. Phone #: ###-#### Inspection requested via web by Stacie Tasker
CHANGE STATUS TO (ISS)  10/27/2017 DONE
(F) Reprint permit  10/27/2017 DONE
INSP-Final Inspection10/25/201710/26/201710/26/2017AFAIL
DetailsTroy Cobbley
Not ready for final yet but we did test two of the three fire smoke dampers and the dry pipe system interconnects. Still waiting on plan modifications, elevator and fire doors.
Plan Modification Accepted  10/26/2017 DONE
Alarm Plan Check10/26/2017 10/26/2017 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  10/26/2017 DONE
Plan mod approved. No additional review comments. All changes to be verified by field inspector.
Permit Ready to Issue  10/26/2017 DONE
Plan Mod Approved, DO NOT REISSUE
INSP-Alarm Testing10/25/201710/25/201710/25/2017PDONE
DetailsTroy Cobbley
See the on site as-builts for devices marked "ok" that have been tested.
INSP-Alarm Testing10/18/201710/19/201710/19/2017ADONE
DetailsTroy Cobbley
For todays inspection I witnessed the corrections for the notification devices and verified sync. and that all notification devices were functional. No initiating devices have been tested. Not all access has been provided for the fire/smoke dampers and not all of the fire sprinkler devices have been connected and pre-tested yet.
INSP-Alarm Testing10/17/201710/18/201710/18/2017PDONE
DetailsTroy Cobbley
We set off the alarms and it mistakenly set off the alarms and shunted the elevator in the ajoining building. Testing was stopped and agreed to reschedule for tomorrow morning.

Phone #: ###-#### Inspection requested via web by Stacie Tasker
Miscellaneous action  10/18/2017 DONE
As built drawings received.
INSP-Final Inspection10/17/201710/17/201710/17/2017PFAIL
DetailsTroy Cobbley
Todays inspection was an initial walk through. I noted that there are two missing horn/strobes in the basement (and a room), one strobe in the basement has been set at 110cd instead of 75cd as shown on the plans, first floor horn/strobes in the south building are incorrectly set at 75cd instead of 15cd, the south building second floor horn/strobe is located too far from the end of the corridor, not all of the fire/smoke dampers have been provided access for verification of correct closure, none of the elevator fire doors are installed, need map, basement manual pull station is mounted too high. We set off the horn, strobes and found that nothing is sync'ing as required by NFPA 72. As-builts are needed showing the changes and will need to be approved by the engineer of record. No actual testing of devices was performed at this time.

Greg Phone #: ###-####
Alarm Plan Check8/1/2016 8/1/2016 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  8/1/2016 PASS
Plans approved with review comments and requirements.
Issue and Print Permit  8/1/2016 DONE
Inspection Record Card- Fire8/1/2016 8/1/2016 DONE
DetailsBrittany Hill
(F) Reprint permit  8/1/2016 DONE
(F) Reprint permit  8/1/2016 DONE
Plan resubmittals received  7/12/2016 DONE
New drawings submitted to address failed pre-screen review.
1st review completed  7/12/2016 FAIL
See 1st review comments.
Plan assigned to (Lee)7/7/2016 7/7/2016 DONE
DetailsLee G Meredith
Miscellaneous action  7/7/2016 DONE
Emailed Mary to let her know that the drawing detail is not clear. Review cannot be done until they are cleaned up. Missing floor plan detail in some areas and excessive detail in others that prevents continuing. Mary indicated that she was not able to get clean drawings from Erstad but upon checking building permit drawings, I found all floor plans to be clear and concise. I informed Mary of this. Submittal returned on pre screen review.
Application received  7/6/2016 DONE
Application submitted via PDS Online on Jul 6 2016 4:45PM