Permit Information
Permit NumberFIR16-00494
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 8303 S FEDERAL WAY
Project NameTHERMO KING INTERMOUNTAIN
Customer Number 
ePlanReviewYes
Description
[Thermo King Intermountain]
The fire sprinkler scope of work consists of installing a complete automatic wet and dry pipe fire sprinkler system throughout the new building per NFPA 13 2013 for light and ordinary hazard, and storage. Work will begin at the connection to the 8" fire stub at the property line and extend 90' of 8" C900 PVC to the riser room.
Plan Mod #1 – 11/02/2016
? Ceiling added in the Compressor Room 109. A pendant head was added below the ceiling.
? The dry sidewall sprinkler was eliminated under the exterior entry canopy outside of Vestibule 100. this entry canopy is all noncombustible and will not be used for storage.
? The Exterior Wash Bay 107 was changed from 3 bays to 4 bays. This required the dry system to be reconfigured. A new hydraulic calculation has been attached to the Plan Mod.
[BLD15-01997] - Permit to construct a new 21,636 square foot office / shop building. This building is fire sprinklered for area increase and utilizes enhanced lighting to comply with the 2012 IECC. Scope of work includes: construction of poured concrete foundation, construction of reinforced CMU exterior walls, construction of new steel bar-joist roof framing / steel pan deck, [construction of interior nonbearing walls to create: service area, cutomer lounge, janitor closet, separate sex accessible restrooms, vestibule, guest office, five individual offices, a conference room, a parts / service counter area, parts warehouse, fire riser room electrical closet, fabrication closet, men’s locker room, and a break room], new electrical, new plumbing, new mechanical, new interior / exterior finishes, new accessible doors / hardware, new front awning, new exterior dock canopy, and related site work. NOTE: a separate racking permit is required and the exterior wash bay is required to be submitted as a Deferred Submittal. This building is fully fire sprinklered for area increase. **TLW**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/16/20172/17/20172/17/2017PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Sprinkler Rough-in/Hydro2/13/20172/13/20172/13/2017PPASS
DetailsJim Page
Hydrostatic test for dry system complete
INSP-Sprinkler Rough-in1/11/20171/11/20171/11/2017PPASS
DetailsJim Page
Rough to cover inspection for overhead fire sprinkler piping/pendant fire sprinkler heads located in the ceiling grid area's complete, overhead fire sprinkler piping in ceiling grid area's approved for cover.
INSP-Sprinkler Rough-in/Hydro1/9/20171/10/20171/10/2017APASS
DetailsJim Page
24 hour air test for dry system complete
INSP-Sprinkler Rough-in/Hydro1/6/20171/9/20171/9/2017APART
DetailsJim Page
Hydrostatic test complete for wet system, 24 hour air test started at 9:30AM with 40 PSI.
INSP-Sprinkler Rough-in/Hydro12/15/201612/15/201612/15/2016PPART
DetailsJim Page
24 dry air system started with 40psi @ 11:00AM. Rough to cover inspection complete for hardlids, cover approved for hardlids.
INSP-Supply line flush11/28/201611/29/201611/29/2016ADONE
DetailsJim Page
Underground supply line flush complete
INSP-Sprinkler Rough-in/Hydro11/7/201611/7/201611/7/2016PPASS
DetailsTroy Cobbley
Underground hydro test passed
Plan Modification Accepted  11/2/2016 DONE
Sprinkler Plan Check11/2/2016 11/2/2016 PASS
DetailsTim Frost
Plan assigned to (Tim)11/2/2016 11/2/2016 DONE
DetailsTim Frost
PLANS/APPL TAKEN TO FRONT DESK  11/2/2016 DONE
CHANGE STATUS TO (ISS)  11/2/2016 DONE
INSP-Sprinkler Rough-in8/22/20168/23/20168/23/2016APASS
DetailsJim Page
FInal inspection for underground piping that is installed passed/complete, underground supply approved for cover.
INSP-Sprinkler Rough-in8/22/20168/22/20168/22/2016PPART
DetailsJim Page
Rough to cover inspection for underground piping installed, thrust block for in building riser will be poured on 23AUG2016, IBR and thrust block will be inspected for rough to cover when complete.
Sprinkler Plan Check8/2/2016 8/2/2016 PASS
DetailsTim Frost
Please, see attached comments.
PLANS/APPL TAKEN TO FRONT DESK  8/2/2016 DONE
DetailsTim Frost
Issue and Print Permit  8/2/2016 DONE
Inspection Record Card- Fire8/2/2016 8/2/2016 DONE
DetailsBrittany Hill
Intake Approval  8/1/2016 PASS
Plan assigned to (Tim)8/1/2016 8/1/2016 DONE
DetailsTim Frost
Sprinkler Plan Check8/1/2016 8/1/2016 FAIL
DetailsTim Frost
1st review completed  8/1/2016 FAIL
DetailsTim Frost
Miscellaneous action  8/1/2016 DONE
DetailsTim Frost
Emailed contractor in regards to failed review.
Application received  7/29/2016 DONE
Application submitted via PDS Online on Jul 29 2016 9:45AM