INSP-Final Inspection | 10/27/2016 | 10/27/2016 | 10/27/2016 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled. Forward flush passed
|
INSP-Final Inspection | 10/26/2016 | 10/26/2016 | 10/26/2016 | P | FAIL |
Troy Cobbley
|
|
|
Need to pass the forward flush as discussed.
|
INSP-Sprinkler Rough-in | 10/25/2016 | 10/25/2016 | 10/25/2016 | P | PASS |
Troy Cobbley
|
|
|
Overhead hydro test passed for the new piping added.
|
Plan Modification Accepted | | | 10/24/2016 | | DONE |
|
|
|
|
Sprinkler Plan Check | 10/24/2016 | | 10/24/2016 | | PASS |
Tim Frost
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/24/2016 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 10/24/2016 | | DONE |
|
|
|
|
CHANGE STATUS TO (ISS) | | | 10/24/2016 | | DONE |
|
|
|
Plan Mod
|
(F) Reprint permit | | | 10/24/2016 | | DONE |
|
|
|
|
INSP-Sprinkler Rough-in/Hydro | 10/21/2016 | 10/21/2016 | 10/21/2016 | P | PART |
Troy Cobbley
|
|
|
Overhead hydro test passed. Forward flush failed. It is required to have 7psi but we only got 3psi. Design static pressure was 55psi but 50psi is showing on the bottom guage.
|
INSP-Supply line flush | 10/13/2016 | 10/13/2016 | 10/13/2016 | P | PASS |
Troy Cobbley
|
|
|
Underground flush passed
|
INSP-Sprinkler Rough-in/Hydro | 10/6/2016 | 10/6/2016 | 10/6/2016 | P | PASS |
Troy Cobbley
|
|
|
Underground hydro test passed.
|
INSP-Sprinkler Rough-in/Hydro | 10/5/2016 | 10/5/2016 | 10/5/2016 | P | CANC |
Troy Cobbley
|
|
|
Christopher// the later the better Phone #: ###-####
|
INSP-Sprinkler Rough-in | 9/30/2016 | 10/3/2016 | 10/3/2016 | P | PASS |
Troy Cobbley
|
|
|
The underground supply piping has been modified to meet the min. bury depth. Piping can be buried.
|
INSP-Sprinkler Rough-in | 9/29/2016 | 9/29/2016 | 9/29/2016 | P | FAIL |
Troy Cobbley
|
|
|
Todays inspection was for the underground supply piping. It failed because the dept. of cover does not meet the minum dept of 4'-6". It is running right around 4'-0"
|
Plan Modification Accepted | | | 9/21/2016 | | DONE |
|
|
|
|
Plan assigned to (Tim) | 9/21/2016 | | 9/21/2016 | | DONE |
Tim Frost
|
|
|
|
Sprinkler Plan Check | 9/21/2016 | | 9/21/2016 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/21/2016 | | DONE |
Tim Frost
|
|
|
|
Permit Ready to Issue | | | 9/21/2016 | | DONE |
|
|
|
no fee due as per Lee Meredith
|
CHANGE STATUS TO (ISS) | | | 9/21/2016 | | DONE |
|
|
|
|
INSP-Sprinkler Rough-in | 9/19/2016 | 9/19/2016 | 9/19/2016 | P | PASS |
Troy Cobbley
|
|
|
Rough-in passed. Piping can be covered. Not all of the walls have been installed yet so final pendant head spacing can not be verified yet.
|
Intake Approval | | | 9/9/2016 | | PASS |
|
|
|
|
Plan assigned to (Tim) | 9/9/2016 | | 9/9/2016 | | DONE |
Tim Frost
|
|
|
|
Sprinkler Plan Check | 9/9/2016 | | 9/9/2016 | | PASS |
Tim Frost
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/9/2016 | | DONE |
Tim Frost
|
|
|
|
Permit Ready to Issue | | | 9/9/2016 | | DONE |
|
|
|
as per Tim no fees due
|
CHANGE STATUS TO (ISS) | | | 9/9/2016 | | DONE |
|
|
|
|
(F) Reprint permit | | | 9/9/2016 | | DONE |
|
|
|
|
INSP-Sprinkler Rough-in/Hydro | 9/7/2016 | 9/7/2016 | 9/7/2016 | P | FAIL |
Troy Cobbley
|
|
|
The installation does not match plans. Resubmittals are required per the review notes due to the safety factor of the hydraulic calculations. I noted numerous pipe routing changes, added fittings and pendant heads spaced at 16' apart. Riser has not been built yet and the underground supply piping has not been installed yet. Rough-in inspection and hydro test stopped due to the issues.
|
Intake Approval | | | 8/3/2016 | | PASS |
|
|
|
|
Plan assigned to (Tim) | 8/3/2016 | | 8/3/2016 | | DONE |
Tim Frost
|
|
|
|
Miscellaneous action | | | 8/3/2016 | | PEND |
|
|
|
*** FIELD INSPECTOR ***
The City of Boise mapping program indicates the underground length to be approximately 96’± not 35’ as shown on the drawing. Please, verify length during underground installation. If the underground is longer than 96' the hydraulic calculations do not work.
|
Sprinkler Plan Check | 8/3/2016 | | 8/3/2016 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
|
1st review completed | | | 8/3/2016 | | PASS |
Tim Frost
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/3/2016 | | DONE |
Tim Frost
|
|
|
|
Permit Ready to Issue | | | 8/3/2016 | | DONE |
|
|
|
|
Issue and Print Permit | | | 8/3/2016 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 8/3/2016 | | 8/3/2016 | | DONE |
Kristal Soland
|
|
|
|
Application received | | | 8/1/2016 | | DONE |
|
|
|
Application submitted via PDS Online on Aug 1 2016 3:22PM
|