Information based on query as of Saturday, June 29, 2024.
Permit Information
Permit NumberFIR16-00520
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 1161 W RIVER ST
Project NameMOUNTAIN WATERWORKS T.I. 1st F
Customer Number 
ePlanReviewYes
Description
[Mountain Waterworks] - Quick Permit
Quick Permit Add, plug and relocate sprinklers to accommodate new wall and ceiling configuration.

[BLD16-02659] - Permit is to remodel an existing 4,282 sq. ft. tenant space on the 1st floor of a 48,000 sq. ft. three story building. Approval is contingent upon adhering to the approved plans on file. Work to include: removal of select interior nonbearing walls, removal of select door/door frames, removal of select millwork, construction of select interior nonbearing walls to create a larger conference room, (4) offices, (3) offices with partial height walls, partial height walls at the open office area, a break room, new select transom windows, new millwork, relocate existing sink, relocating select existing light fixtures, adding select new light fixtures, some plumbing work, electrical work and interior finishes to be in compliance with Ch. 8 of the 2012 IBC. This building is fully Fire Sprinklered with an approved Fire Alarm system. Any alterations or modifications to the buildings Fire Sprinkler or Fire Alarm system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA 13 & NFPA 72 as regulated by the Boise Fire Department. **JG**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/21/20169/21/20169/21/2016APASS
DetailsJim Page
Final fire sprinkler inspection passed/complete
INSP-Sprinkler Rough-in8/22/20168/23/20168/22/2016APASS
DetailsJim Page
Rough to cover inspection for overhead fire sprinkler piping complete, overhead fire sprinkler piping per this area of work approved for cover.
INSP-Sprinkler Rough-in8/18/20168/19/20168/19/2016AFAIL
DetailsJim Page
Rough to cover inspection complete, if no other walls/lintel are installed for the breakroom then small room rule does not apply, fire sprinkler are 8ft off of wall. Office on southside of tenant space has heads 9ft 6in off of wall, small room rule can apply to these heads but max distance is 9ft off of one wall.
Intake Approval  8/9/2016 PASS
Plan assigned to (Tim)8/9/2016 8/9/2016 DONE
DetailsTim Frost
Sprinkler Plan Check8/9/2016 8/9/2016 PASS
DetailsTim Frost
Please, see attached comments.
1st review completed  8/9/2016 PASS
DetailsTim Frost
PLANS/APPL TAKEN TO FRONT DESK  8/9/2016 DONE
DetailsTim Frost
Permit Ready to Issue  8/9/2016 DONE
Issue and Print Permit  8/9/2016 DONE
Inspection Record Card- Fire8/9/2016 8/9/2016 DONE
DetailsCandy A. Nichols
Application received  8/8/2016 DONE
Application submitted via PDS Online on Aug 8 2016 11:59AM