INSP-Final Inspection | 7/24/2019 | 7/25/2019 | 7/25/2019 | A | PASS |
Jim Page
|
|
|
Final fire sprinkler inspection for area of work complete.
Please call Clarence at ###-#### Phone #: ###-#### Inspection requested via web by Jessia Maxwell
|
INSP-Final Inspection | 4/12/2019 | 4/12/2019 | 4/12/2019 | P | CANC |
Jim Page
|
|
|
Per conversation with my supervisor, Adele Schaffeld-Griffin, notes entered reading "Final fire sprinkler sign off of inspections for this permit will be completed at the same time as the life safety inspection is completed under the building permit." Please coordination with the general contractor to schedule the final inspections. Onsite inspection request for today will need to be rescheduled until coordinated inspections for the life safety can be scheduled.
Clarence Phone #: ###-####
|
INSP-Final Inspection | 6/30/2017 | 6/30/2017 | 6/30/2017 | P | PART |
Jim Page
|
|
|
Final fire sprinkler inspection for this permit is complete, permit will remain in issued status until construction for this permitted area is complete.
|
Fees Due Hold | 6/17/2017 | | 6/30/2017 | | DONE |
Christina Prado
|
|
|
|
Fees Due Hold | 6/9/2017 | | 6/16/2017 | | DONE |
Christina Prado
|
|
|
|
INSP-Sprinkler Rough-in/Hydro | 6/8/2017 | 6/9/2017 | 6/9/2017 | A | PASS |
Jim Page
|
|
|
Hydrostatic test for systems 10-2 and 10-6 complete.
|
INSP-Sprinkler Rough-in/Hydro | 6/8/2017 | 6/8/2017 | 6/8/2017 | P | CANC |
Jim Page
|
|
|
Hydrostatic test cancelled by contractor, Chris ###-####
|
Fees Due Hold | 6/3/2017 | | 6/8/2017 | | DONE |
Christina Prado
|
|
|
|
Sprinkler Plan Check | 6/2/2017 | | 6/2/2017 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/2/2017 | | DONE |
Tim Frost
|
|
|
|
Permit Ready to Issue | | | 6/2/2017 | | DONE |
|
|
|
|
Issue and Print Permit | | | 6/2/2017 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 6/2/2017 | | 6/2/2017 | | DONE |
Christina Prado
|
|
|
|
Telephone call | | | 2/27/2017 | | DONE |
Tim Frost
|
|
|
Applicant working on providing letter from RDP verifying and qualifying the exclusion of fire protection in the mechanical chase and interstitial areas; as per NFPA 13-22.23.1.2.1.
|
Miscellaneous action | | | 2/16/2017 | | DONE |
|
|
|
On hold awaiting revision letter.
|
Sprinkler Plan Check | 2/16/2017 | | 2/16/2017 | | FAIL |
Tim Frost
|
|
|
|
Miscellaneous action | | | 2/16/2017 | | DONE |
Tim Frost
|
|
|
Emailed contractor in regards to failed review.
|
Sprinkler Plan Check | 12/23/2016 | | 12/23/2016 | | FAIL |
Tim Frost
|
|
|
|
Plan resubmittals received | | | 12/23/2016 | | DONE |
|
|
|
|
Plan assigned to (Tim) | 12/23/2016 | | 12/23/2016 | | DONE |
Tim Frost
|
|
|
|
Sprinkler Plan Check | 8/30/2016 | | 8/30/2016 | | FAIL |
Tim Frost
|
|
|
Please, see attached comments.
|
1st review completed | | | 8/30/2016 | | FAIL |
|
|
|
|
Miscellaneous action | | | 8/30/2016 | | DONE |
Tim Frost
|
|
|
Emailed contractor in regards to failed review.
|
Intake Approval | | | 8/29/2016 | | PASS |
|
|
|
|
Plan assigned to (Tim) | 8/29/2016 | | 8/29/2016 | | DONE |
Tim Frost
|
|
|
|
Application received | | | 8/22/2016 | | DONE |
|
|
|
Application submitted via PDS Online on Aug 22 2016 4:58PM
|