Information based on query as of Sunday, June 30, 2024.
Permit Information
Permit NumberFIR16-00555
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 4481 W WILLOW LN
Project NameWCA APARTMENTS
Customer Number 
ePlanReviewYes
Description
[Serena House]
The fire sprinkler scope of work consists of providing a NFPA 13 system for a new transition housing building. This is a new two story apartment building but due to a 20’ dead end corridor the building is protected per NFPA 13 NOT NFPA 13R. There is a wet system for the lower floor and a dry system for the upper floor. The system is supplied by 6” underground piping to a 4” backflow preventer through a 4” header to a 2” wet valve and a 3” dry valve. Due to the distance to the nearest hydrant the FDC is located remotely and is shown on the underground drawing.

The underground piping is under permit FIR16-00464

[BLD16-01427] - The fire sprinkler system per NFPA 13 is used to allow dead end corridors more than 20 feet long and as required for R-2 Occupancies. To construct a 10,382 square foot building (5,355 square feet 1st story and 5,027 square feet 2nd story) to be used for transitional housing for women and children (4,492 square feet 1st story and 4,264 square feet 2nd story) and for offices (762 square feet 1st story and 719 square feet 2nd story). Work is to include concrete footings, concrete foundation, concrete slab on grade, wood stud exterior walls, interior and exterior shear walls, interior and exterior bearing walls, wood floor joists, wood roof trusses, wood sheathing for floor and roof diaphragms, asphalt shingles, wood siding, fiber cement siding, exterior windows, exterior doors, one interior stairway, one interior stairway rated like a corridor, one exterior stairway, interior fire-rated corridors, interior nonbearing walls, interior doors, millwork, and interior finishes. The restroom that serves the office area is required to be accessible to the disabled. Two sleeping rooms and their restrooms on the 1st story are required to comply as accessible units. All other sleeping rooms and their restrooms on the 1st story are required to comply as Type B sleeping units. Special Inspection required for soils, concrete, welding, wood diaphragms, and wood shear walls. Metal plate wood trusses are a deferred submittal item. New concrete steps and handrails, a new trash enclosure, and a new 250 square foot storage shed will be constructed at or near the existing “T” shaped building. The work is required to comply with the approved drawings, with the plan review report, with the structural design, and with all applicable codes and ordinances. The fire sprinkler system is required to comply with NFPA 13 and the fire alarm system, if provided, is required to comply with NFPA 72 as regulated by the Fire Department. Separate fire sprinkler permits and fire alarm permits shall be obtained prior to beginning any modification or installation work on such systems. **CJW**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/5/201612/6/201612/6/2016PPASS
DetailsJim Page
Final fire sprinkler inspection passed/complete.
INSP-Final Inspection11/22/201611/23/201611/23/2016ACANC
DetailsJim Page
Inspection request cancelled per conversation with Mike Martin Phone #: ###-#### , inspection will be rescheduled for a later date.
INSP-Sprinkler Rough-in/Hydro11/21/201611/21/201611/21/2016PPASS
DetailsJim Page
24 hour test for dry system complete, hydrostatic test for dry system/level 2 sprinklers complete
INSP-Sprinkler Rough-in11/17/201611/18/201611/18/2016APART
DetailsJim Page
24 hour air test started at 2:50pm with 42psi.
INSP-Sprinkler Rough-in/Hydro11/17/201611/18/201611/18/2016PCANC
DetailsJim Page
Hydrostatic test to be rescheduled for monday, 21NOV2016
INSP-Sprinkler Rough-in10/7/201610/10/201610/10/2016APASS
DetailsJim Page
Partial rough to cover inspection complete for overhead fire sprinkler piping located on level 2 dry system, notated the city approved drawings with yellow highlighter/red ink for area's approved for cover. Noted that the city approved drawings are allowing return bends with regular pendant heads in place of dry pendant sprinkler heads on the attic dry system, verified this install method with plan reviewer (This is not a normal practice for pendant install on a dry system). City approved drawings state "Tenting of return bends in lieu of dry pendant sprinklers was approved by the fire marshal's office" Tenting inspection has been completed for return bends and pendant heads on level 2 dry system.
INSP-Sprinkler Rough-in/Hydro10/6/201610/7/201610/7/2016APASS
DetailsJim Page
Hydrostatic test for overhead fire sprinkler piping on level 1 complete. Hydrostatic test for remote FDC complete.
INSP-Sprinkler Rough-in9/26/20169/26/20169/26/2016PPASS
DetailsJim Page
Rough to cover inspection for overhead fire sprinkler piping located on level 1 complete, overhead fire sprinkler piping on level 1 approved for cover.
Plan Modification Accepted  9/15/2016 DONE
Plan assigned to (Tim)9/15/2016 9/15/2016 DONE
DetailsTim Frost
PLANS/APPL TAKEN TO FRONT DESK  9/15/2016 DONE
CHANGE STATUS TO (ISS)  9/15/2016 DONE
Sprinkler Plan Check9/7/2016 9/7/2016 PASS
DetailsTim Frost
Please, see attached comments.
PLANS/APPL TAKEN TO FRONT DESK  9/7/2016 DONE
DetailsTim Frost
Permit Ready to Issue  9/7/2016 DONE
Issue and Print Permit  9/7/2016 DONE
Inspection Record Card- Fire9/7/2016 9/7/2016 DONE
DetailsCandy A. Nichols
Intake Approval  8/30/2016 PASS
Plan assigned to (Tim)8/30/2016 8/30/2016 DONE
DetailsTim Frost
Sprinkler Plan Check8/30/2016 8/30/2016 FAIL
DetailsTim Frost
1st review completed  8/30/2016 FAIL
DetailsTim Frost
Miscellaneous action  8/30/2016 DONE
DetailsTim Frost
Emailed contractor in regards to failed review.
Application received  8/24/2016 DONE
Application submitted via PDS Online on Aug 24 2016 11:20AM