Permit Information
Permit NumberFIR16-00594
StatusIssued
Name STATEFIRE DC SPECIALTIES
Site Address 100 S 6TH ST
Project NameChina Blue Fire Alarm Replace
Customer Number 
ePlanReviewYes
Description
Replace existing Edwards EST2 fire alarm panel and annunciator with a new Edwards IO-64 fire alarm panel and annunciator. This work is not associated with a building permit.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/17/20171/17/20171/17/2017PPASS
DetailsScott Arellano
Performed test and witnessed all levels successfully stop audible entertainment with full audible and visual fire alarm notification activated.
INSP-Final Inspection1/4/20171/4/20171/4/2017PPART
DetailsJim Page
Partial final inspection complete for fire alarm system, city approved drawings match the installation. Need to verify audio shutdown on DJ equipment during a fire alarm event, permit cannot be finaled until audio shutdown is inspected and passed.
INSP-Final Inspection12/29/201612/30/201612/30/2016AFAIL
DetailsJim Page
Audio visual devices tested and inspected, all tested correctly. On-site city approved drawings do not match the system installed, approved drawings show numerous smoke detectors throughout space and the smoke detectors have been reomved. A city approved drawing needs to be provided showing the removal of the devices or the system will need to match what was submitted.
CHANGE STATUS TO (ISS)  11/18/2016 DONE
Plan resubmittals received  11/17/2016 DONE
Plan modification showing all changes.
CHANGE STATUS TO (REV)  11/17/2016 DONE
1st review completed  11/17/2016 PASS
Alarm Plan Check11/17/2016 11/17/2016 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  11/17/2016 DONE
Resubmittal of plan modification approved. No additional review comments.
Permit Ready to Issue  10/20/2016 DONE
Issue and Print Permit  10/20/2016  
Inspection Record Card- Fire10/20/2016 10/20/2016 DONE
DetailsChristina Prado
Miscellaneous action  9/29/2016 DONE
Email from Kenny: Thank you for the confirmation Lee. I received approval from Tom Gainer to remove the door holders on the 3 doors in the stairway. Therefore, we will resubmit showing those and their smoke detectors removed. We will also be removing the pull stations, adding one by the riser, and moving the elevator smokes over about 8-10 feet as we discussed.
Telephone call  9/28/2016 DONE
Kenny called to see if manual pull stations were required. I informed him that since it is fully sprinklered, only one was required and that if the owner would rather not have them, they could be excluded. This would require updated as built drawings at the time of completion.
Alarm Plan Check9/28/2016 9/28/2016 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  9/28/2016 DONE
Plans approved with review comments and requirements.
Plan resubmittals received  9/26/2016 DONE
1st review completed  9/23/2016 FAIL
Notification inadequate, heat substituted for a required smoke, notification product datat missing. See review comments.
Miscellaneous action  9/23/2016 DONE
Emailed Kenny to also let him know that the existing sound systems will be required to have a shunt interface to stop or reduce ambient background sound levels.
Plan assigned to (Lee)9/22/2016 9/22/2016 DONE
DetailsLee G Meredith
Miscellaneous action  9/22/2016 DONE
Failed on pre-screen review. Kenny was directed to seperate drawings into individual files.
Application received  9/19/2016 DONE
Application submitted via PDS Online on Sep 19 2016 10:16AM