Permit Information
Permit NumberFIR16-00617
StatusFinaled
Name LOCAL FIRE AND SECURITY
Site Address 901 N CURTIS RD Unit: 304
Project NameIdaho Hand Center, suite #304
Customer Number 
ePlanReviewYes
Description
Revise existing notification within the TI to accommodate appropriate visual coverage. Associated with building permit BLD16-02814.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Alarm Testing12/15/201612/16/201612/16/2016PPASS
DetailsTroy Cobbley
permit finaled
DOC - Permit Finaled  12/16/2016 DONE
Per Troy good to final
INSP-Final Inspection12/12/201612/15/201612/15/2016AFAIL
DetailsTroy Cobbley
The notification devices functioned correctly. I had Brian field adjust two to meet spacing requirements for room method. As-builts required. We started to test the fire/smoke dampers and found that not all are accessible and atleast two have been wired backwards.
Application received  9/29/2016 DONE
Application submitted via PDS Online on Sep 29 2016 12:28PM
Plan assigned to (Lee)9/29/2016 9/29/2016 DONE
DetailsLee G Meredith
1st review completed  9/29/2016 PASS
Alarm Plan Check9/29/2016 9/29/2016 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  9/29/2016 DONE
Plans approved with review comments.
Permit Ready to Issue  9/29/2016 DONE
Issue and Print Permit  9/29/2016 DONE
Inspection Record Card- Fire9/29/2016 9/29/2016 DONE
DetailsBrittany Hill