INSP-Final Inspection | 12/2/2016 | 12/2/2016 | 12/2/2016 | P | PASS |
Troy Cobbley
|
|
|
Pemit finaled
|
Alarm Plan Check | 12/1/2016 | | 12/1/2016 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 12/1/2016 | | DONE |
|
|
|
Plans approved with review comments and drawing notation.
|
Permit Ready to Issue | | | 12/1/2016 | | DONE |
|
|
|
|
Issue and Print Permit | | | 12/1/2016 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 12/1/2016 | | 12/1/2016 | | DONE |
Kristal Soland
|
|
|
|
Plan resubmittals received | | | 11/30/2016 | | DONE |
|
|
|
|
1st review completed | | | 10/24/2016 | | FAIL |
|
|
|
Fire alarm plans don't match building permit plans. Resubmittal required.
|
Telephone call | | | 10/21/2016 | | DONE |
|
|
|
Telephoned Rand for an update on resubmittal status. He indicated that he has a new quote to the general contractor for additional work that he was not previously aware of and will resubmit once approved.
|
Plan resubmittals received | | | 10/17/2016 | | DONE |
|
|
|
Resubmittals received with correction made. In verifying related building permit drawings, I found floor plans did not match. I emailed Rand to request an explanation.
|
Plan assigned to (Lee) | 10/14/2016 | | 10/14/2016 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 10/14/2016 | | FAIL |
|
|
|
Scale is incorrect and strobe spacing does not meet current NFPA 72 spacing requirements.
|
Application received | | | 10/3/2016 | | DONE |
|
|
|
Application submitted via PDS Online on Oct 3 2016 12:54PM
|