Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberFIR16-00628
StatusFinaled
Name PROTEX
Site Address 6000 W DENTON ST
Project NameCascadia Healthcare
Customer Number 
ePlanReviewYes
Description
Install a code-compliant fire alarm system in new construction. Sprinkler monitoring, fire damper closure and common area notification with sounder bases in individual rooms. Associated with building permit BLD16-01757.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/1/20183/2/20183/2/2018PPASS
DetailsTroy Cobbley
Permit finaled

Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
Miscellaneous action  2/22/2018 DONE
Received revised drawings showing the location of 7 fire smoke dampers with in duct detection.
INSP-Final Inspection2/20/20182/21/20182/21/2018AFAIL
DetailsTroy Cobbley
Need the fire/smoke dampers (smoke detectors), connected to the fire alarm system. Devices need to be tested when installed.

Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
INSP-Final Inspection2/19/20182/20/20182/20/2018APART
DetailsTroy Cobbley
Today we verified function of various room detectors, two of the three roof top units and the delayed egress doors. I noted that one hvac unit did not function and I need verification that the spot type detector being utilized is listed for the max air flow expected in the hvac unit, the southwest delayed egress door did not function.
Miscellaneous action  2/20/2018 DONE
Received updated riser and floor plan from Morgan.
Miscellaneous action  2/15/2018 DONE
Received an updated operational matrix from Morgan.
INSP-Final Inspection2/12/20182/13/20182/13/2018PPART
DetailsTroy Cobbley
I verified head end equipment and smoke detectors for door release in the corridors. One pair of doors did not latch. There are delayed egress doors installed that will need to be connected to the fire alrm system for releaseas per the IFC. The accordian fire doors have not been installed yet. Still need to test devices in the individual rooms. The sounder bases in the individual rooms need to sound upon genereal alarm (see alarm matrix). Need to test the fire sprinkler devices and the duct detectors for hvac unit shutdown. Signals have been verified for the devices tested today.

Contact is Dirk Phone #: ###-#### Inspection requested via web by Morgan Ahten
Miscellaneous action  2/13/2018 DONE
Updated as built riser received from Morgan.
Miscellaneous action  2/12/2018 DONE
Morgan sent and updated floor plan as directed by Troy.
INSP-Final Inspection2/7/20182/9/20182/9/2018AFAIL
DetailsTroy Cobbley
Plan modifications are needed for all of the changes required. There are many locations where strobes are over spaced including the Common Areas and in the Sleeping Rooms. Panels have been relocated. Smoke detectors for door release need to be centered on the door and with-in 5'-0" of the door and more than 3'-0" from air diffusers. Strobes need to be added in acouple locations.

Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
Miscellaneous action  2/9/2018 DONE
Riser drawing as built received and uploaded to eplanreview.
Miscellaneous action  10/25/2016 DONE
Changed address from 711 N Curtis Rd
Permit Ready to Issue  10/14/2016 DONE
Issue and Print Permit  10/14/2016 DONE
Inspection Record Card- Fire10/14/2016 10/14/2016 DONE
DetailsChristina Prado
Plan assigned to (Lee)10/13/2016 10/13/2016 DONE
DetailsLee G Meredith
1st review completed  10/13/2016 PASS
Alarm Plan Check10/13/2016 10/13/2016 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  10/13/2016 DONE
Plans approved with review comments.
Application received  10/4/2016 DONE
Application submitted via PDS Online on Oct 4 2016 10:07AM