INSP-Final Inspection | 1/17/2017 | 1/18/2017 | 1/18/2017 | P | PASS |
Troy Cobbley
|
|
|
permit finaled
|
INSP-Final Inspection | 1/17/2017 | 1/17/2017 | 1/17/2017 | P | FAIL |
Troy Cobbley
|
|
|
Need as-builts showing cellular dialer instead of phone lines and the two new tamper switches and the two fire sprinkler tamper switches wired in/tested.
|
INSP-Final Inspection | 1/12/2017 | 1/13/2017 | 1/13/2017 | P | CANC |
Troy Cobbley
|
|
|
Not ready for final due to the project related sprinkler permits. Need document box as discussed.
|
Permit Ready to Issue | | | 10/18/2016 | | DONE |
|
|
|
|
Issue and Print Permit | | | 10/18/2016 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 10/18/2016 | | 10/18/2016 | | DONE |
Candy A. Nichols
|
|
|
|
Plan assigned to (Lee) | 10/14/2016 | | 10/14/2016 | | DONE |
Lee G Meredith
|
|
|
|
Miscellaneous action | | | 10/14/2016 | | DONE |
|
|
|
Central station inteface not shown on the drawings. Contacted Mary for information. She confirmed interface is through phone lines.
|
1st review completed | | | 10/14/2016 | | PASS |
|
|
|
|
Alarm Plan Check | 10/14/2016 | | 10/14/2016 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 10/14/2016 | | DONE |
|
|
|
Plans approved with review comments.
|
Application received | | | 10/12/2016 | | DONE |
|
|
|
Application submitted via PDS Online on Oct 12 2016 10:50AM
|