INSP-Final Inspection | 12/28/2016 | 12/29/2016 | 12/29/2016 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
CHANGE STATUS TO (ISS) | | | 12/28/2016 | | DONE |
Christina Prado
|
|
|
|
Miscellaneous action | | | 12/15/2016 | | DONE |
|
|
|
Rose emailed comments from the owner that indicated the generator room is not required by NEC to be explosion proof. Review comments were re-issued to reflect this.
|
INSP-Final Inspection | 12/9/2016 | 12/13/2016 | 12/13/2016 | A | FAIL |
Troy Cobbley
|
|
|
No approval notes were provided. Once they were found online I pointed out the requirement for explosion proof items. Also needed are the record of completions, as-builts showing the manual pull station change and an updated map. Items did test ok.
|
Miscellaneous action | | | 12/13/2016 | | DONE |
|
|
|
Rose emailed a request to omit the explosion proof installation requirements noted in the review comments. I informed her to provide documentation indicating that this is not needed per NEC requirements.
|
Plan resubmittals received | | | 12/9/2016 | | DONE |
|
|
|
|
CHANGE STATUS TO (REV) | | | 12/9/2016 | | DONE |
|
|
|
|
Alarm Plan Check | 12/9/2016 | | 12/9/2016 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 12/9/2016 | | DONE |
|
|
|
Resubmittal approved with requirements noted on drawing. No new review comments.
|
Permit Ready to Issue | | | 12/9/2016 | | DONE |
|
|
|
please do notre issue
|
Telephone call | | | 12/9/2016 | | DONE |
|
|
|
Rose called to indicate that the Verizon engineers wanted to change the design so notification will no longer activate horn strobe notification. She requested the workflow be restarted so she could upload plan modificaitons that show the changes.
|
1st review completed | | | 11/7/2016 | | PASS |
|
|
|
|
Alarm Plan Check | 11/7/2016 | | 11/7/2016 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 11/7/2016 | | DONE |
|
|
|
Plans approved with review comments and drawing notation.
|
Permit Ready to Issue | | | 11/7/2016 | | DONE |
|
|
|
|
Issue and Print Permit | | | 11/7/2016 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 11/7/2016 | | 11/7/2016 | | DONE |
Christina Prado
|
|
|
|
Plan assigned to (Lee) | 11/3/2016 | | 11/3/2016 | | DONE |
Lee G Meredith
|
|
|
|
Miscellaneous action | | | 11/3/2016 | | DONE |
|
|
|
Exploded view for area of work does not have a scale reference. I requested the room dimensions from Rose. She supplied the information on 11-4-16.
|
Application received | | | 11/2/2016 | | DONE |
|
|
|
Application submitted via PDS Online on Nov 2 2016 3:59PM
|