INSP-Final Inspection | 11/16/2017 | 11/16/2017 | 11/16/2017 | P | PASS |
Jim Page
|
|
|
Final fire alarm inspection passed/complete
|
INSP-Final Inspection | 11/15/2017 | 11/16/2017 | 11/16/2017 | A | PART |
Jim Page
|
|
|
Fire sprinkler tamper switches are complete, flow switch on east system in riser room leaked while water was flowing, can not complete fire alarm inspection until flow switch is replaced.
|
INSP-Final Inspection | 11/14/2017 | 11/15/2017 | 11/15/2017 | A | CANC |
Jim Page
|
|
|
Fire alarm inspection could not be done due to underground supply to building not being turned on, inspection will need to be rescheduled. This inspection request is cancelled.
|
Permit Ready to Issue | | | 12/1/2016 | | DONE |
|
|
|
all requirments met
|
Issue and Print Permit | | | 12/1/2016 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 12/1/2016 | | 12/1/2016 | | DONE |
Carlos Velazquez
|
|
|
|
Application received | | | 11/30/2016 | | DONE |
|
|
|
Application submitted via PDS Online on Nov 30 2016 2:44PM
|
Plan assigned to (Lee) | 11/30/2016 | | 11/30/2016 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 11/30/2016 | | PASS |
|
|
|
|
Alarm Plan Check | 11/30/2016 | | 11/30/2016 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 11/30/2016 | | DONE |
|
|
|
Plans approved with review comments.
|