Permit NumberFIR17-00007
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 7700 W STATE ST
Project NameNative Grill and Wings
Customer Number 
ePlanReviewYes
Description
[Native Grill and Wings - North Pointe]
The fire sprinkler scope of work consists of a tenant improvement. The new tenant will be a restaurant. Upright and pendent sprinklers are being armed over due to new walls and lighting.

Contractor’s Note:
The building permit has not been issued at this time. The building department may determine that changes are required to the building plans in order to meet code. The changes may affect the sprinkler system. The sprinkler contractor will be obligated to make all necessary changes that may be required. Therefore, if the sprinkler contractor chooses to proceed without an issued building permit, they will do so on their own cognizance. This note does not constitute an early start agreement.

[BLD16-03951] – The fire sprinkler system is used for occupancy. To construct interior tenant improvements for a new 5,090 square foot restaurant tenant within a 7,222 square foot building. In addition to the interior, a 514 square foot fenced patio below an exterior trellis will also be prepared for occupancy. Work is to include interior nonbearing walls, 2 restrooms accessible to the disabled, a commercial kitchen, kitchen equipment, a bar, bar equipment, built in elevated benches mounted on concrete bases, tables, chairs, booths, millwork, patio fences, patio gates, and finishes. Two Type I grease hoods each having their own grease exhaust duct system will be installed. The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes and ordinances. Work within the adjacent tenant space will be covered under a separate future permit. The fire sprinkler system is required to comply with NFPA 13 and the fire alarm system is required to comply with NFPA 72 as regulated by the Fire Department. Separate fire sprinkler permits and fire alarm permits shall be obtained prior to beginning any modification or installation work on such systems. **CJW**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/27/20172/28/20172/28/2017APASS
DetailsJim Page
Final fire sprinkler inspection passed/complete
INSP-Sprinkler Rough-in2/17/20172/21/20172/21/2017APASS
DetailsJim Page
Rough to cover inspection for overhead fire sprinkler piping located in area of work complete, area of work approved for cover. Noted that the fire sprinkler heads located next to the commercial cooking hood are 155 degree heads, recommend that the heads around the cooking hood be changed to 200 degree heads due to heat from cooking appliances.
Sprinkler Plan Check1/11/2017 1/11/2017 PASS
DetailsTim Frost
Please, see attached comments.
PLANS/APPL TAKEN TO FRONT DESK  1/11/2017 DONE
DetailsTim Frost
Permit Ready to Issue  1/11/2017 DONE
Issue and Print Permit  1/11/2017 DONE
Inspection Record Card- Fire1/11/2017 1/11/2017 DONE
DetailsChristina Prado
Intake Approval  1/6/2017 PASS
Plan assigned to (Tim)1/6/2017 1/6/2017 DONE
DetailsTim Frost
Application received  1/5/2017 DONE
Application submitted via PDS Online on Jan 5 2017 4:32PM