INSP-Final Inspection | 4/19/2017 | 4/20/2017 | 4/20/2017 | A | PASS |
Jim Page
|
|
|
Final fire alarm inspection passed/complete
|
Permit Ready to Issue | | | 1/31/2017 | | DONE |
|
|
|
|
Issue and Print Permit | | | 1/31/2017 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 1/31/2017 | | 1/31/2017 | | DONE |
Christina Prado
|
|
|
|
Plan assigned to (Lee) | 1/30/2017 | | 1/30/2017 | | DONE |
Lee G Meredith
|
|
|
|
Telephone call | | | 1/30/2017 | | DONE |
|
|
|
Called Ken to inform hime that based on some corridors being non-rated, there is a requriement for either smoke detection in those corridors OR quick response sprinklers throughout the floors that have non-rated corridors. Informed him that I would note this on the drawing and review but leave it up to the contractors to determine which is to be supplied. All changes related to this will reqire resubmittal.
|
1st review completed | | | 1/30/2017 | | PASS |
|
|
|
|
Alarm Plan Check | 1/30/2017 | | 1/30/2017 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 1/30/2017 | | DONE |
|
|
|
Plans approved with review comments and requirements.
|
Application received | | | 1/28/2017 | | DONE |
|
|
|
Application submitted via PDS Online on Jan 28 2017 9:46AM
|