INSP-Final Inspection | 8/13/2019 | 8/13/2019 | 8/13/2019 | P | PASS |
Jim Page
|
|
|
Final fire sprinkler inspection for scope of work has been completed. Drop downs have been added for future obstruction install, as of these notes it is not clear when obstructions will be placed, a seperate permit will be requested when obstructions are designed and placed. A temp overhead door has been added as well as an open vent grate on the exterior wall, need coverage under overhead door and verify that the sprinkler piping next to open exterior vent will not freeze due to vent being exposed to outside atmosphere. Noted items will need to be addressed before life fire safety inspection. A seperate permit will be required for items noted.
|
INSP-Sprinkler Rough-in/Hydro | 8/13/2019 | 8/13/2019 | 8/13/2019 | P | DONE |
Jim Page
|
|
|
Hydrostatic test for this system has been witnessed, no pressure loss was observed.
|
INSP-Sprinkler Rough-in | 8/13/2019 | 8/13/2019 | 8/13/2019 | P | PASS |
Jim Page
|
|
|
Rough in inspection for this system has been completed. Drop downs for obstruction coverage are in place but obstructions have not been installed.
|
Fees Due Hold | 6/17/2017 | | 9/13/2017 | | DONE |
Brittany Hill
|
|
|
|
Fees Due Hold | 6/15/2017 | | 6/16/2017 | | DONE |
Christina Prado
|
|
|
|
Sprinkler Plan Check | 6/14/2017 | | 6/14/2017 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/14/2017 | | DONE |
Tim Frost
|
|
|
|
Permit Ready to Issue | | | 6/14/2017 | | DONE |
|
|
|
|
Issue and Print Permit | | | 6/14/2017 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 6/14/2017 | | 6/14/2017 | | DONE |
Christina Prado
|
|
|
|
Intake Approval | | | 3/7/2017 | | PASS |
|
|
|
|
Plan assigned to (Tim) | 3/7/2017 | | 3/7/2017 | | DONE |
Tim Frost
|
|
|
|
Sprinkler Plan Check | 3/7/2017 | | 3/7/2017 | | FAIL |
Tim Frost
|
|
|
|
1st review completed | | | 3/7/2017 | | FAIL |
Tim Frost
|
|
|
|
Miscellaneous action | | | 3/7/2017 | | DONE |
Tim Frost
|
|
|
Emailed contractor in regards to failed review.
|
Application received | | | 2/26/2017 | | DONE |
|
|
|
Application submitted via PDS Online on Feb 26 2017 3:57PM
|