INSP-Final Inspection | 4/25/2017 | 4/25/2017 | 4/25/2017 | A | PASS |
Jim Page
|
|
|
Final fire alarm inspection passed/complete
|
INSP-Final Inspection | 4/12/2017 | 4/14/2017 | 4/14/2017 | A | FAIL |
Troy Cobbley
|
|
|
Everything tested ok. Permit is ok to final when the as-builts have been received by plan review.
|
INSP-Final Inspection | 4/11/2017 | 4/12/2017 | 4/12/2017 | A | FAIL |
Troy Cobbley
|
|
|
No testing performed. All strobes are overspaced.
|
Plan resubmittals received | | | 3/13/2017 | | DONE |
|
|
|
|
Alarm Plan Check | 3/13/2017 | | 3/13/2017 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 3/13/2017 | | DONE |
|
|
|
Plans approved with review comments.
|
Permit Ready to Issue | | | 3/13/2017 | | DONE |
|
|
|
all requirements met
|
Issue and Print Permit | | | 3/13/2017 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 3/13/2017 | | 3/13/2017 | | DONE |
Carlos Velazquez
|
|
|
|
Miscellaneous action | | | 3/6/2017 | | DONE |
|
|
|
Emailed Dave to remind him to do the upload complete task.
|
Miscellaneous action | | | 3/6/2017 | | DONE |
|
|
|
Uploads finally received.
|
Miscellaneous action | | | 3/6/2017 | | DONE |
|
|
|
Design shows 3 existing horn strobes that were relocated in a vanilla TI of an unoccupied suite. Candela settings shown do not meet NFPA 72 spacing requirements. Dave Oliver of AEI was informed that even thought the devices are not required in an unoccupied space, they must be installed properly if they are provided. Dave will revise the design and provide new drawings and calcs.
|
Plan assigned to (Lee) | 3/6/2017 | | 3/6/2017 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 3/6/2017 | | FAIL |
|
|
|
|
Application received | | | 3/2/2017 | | DONE |
|
|
|
Application submitted via PDS Online on Mar 2 2017 2:28PM
|