Permit Information
Permit NumberFIR17-00178
StatusFinaled
Name MICRON TECHNOLOGY INC FA
Site Address 8000 S FEDERAL WAY
Project NameC24074 B51 R & D Expansion
Customer Number 
ePlanReviewYes
Description
C24074 B51 R & D Expansion is a 100,000sf. free standing expansion of Microns Research and Development Facilities, and an extension of the previously constructed B50. Associated with building permit BLD16-03440.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/30/20207/31/20207/31/2020APASS
DetailsJim Page
Final fire alarm inspection is complete.

Screened- Dillon Phone #: ###-####
INSP-Final Inspection5/20/20205/21/20205/21/2020APART
DetailsJim Page
Final fire alarm inspection for pyrophoric building is complete, fire alarm permit covers entire B51 building to include pyrophonic building, fire alarm permit will remain in issued status until entire FIR permit scope is inspected.

Dillin *screened* Phone #: ###-####
Fees Due Hold4/25/2020 5/20/2020 DONE
DetailsTiffany Carson-Herker
INSP-Alarm Testing4/27/20204/27/20204/27/2020PDONE
DetailsTroy Cobbley
I helped Jim Page out on this inspection. Please see the city approved plans for corrections notated.
INSP-Alarm Testing4/24/20204/27/20204/27/2020APART
DetailsJim Page
Fire alarm walkthrough partially complete, city approved plans have been notated for areas to correct.

screened // Dillon Phone #: ###-####
INSP-Alarm Testing4/23/20204/24/20204/24/2020APART
DetailsJim Page
Fire alarm walkthrough partially complete, city approved plans have been notated for areas to correct.

*screened* Dillon Phone #: ###-####
INSP-Alarm Testing4/22/20204/23/20204/23/2020APART
DetailsJim Page
Walk through for level 3 complete, notated city approved drawings areas needing correction, 4 areas total for level 3.

dillon Phone #: ###-####
Permit Ready to Issue  3/25/2020 DONE
as built approved
CHANGE STATUS TO (ISS)  3/25/2020 DONE
Plan assigned to (Lee)3/2/2020 3/24/2020 DONE
DetailsLee G Meredith
1st review completed  3/24/2020 DONE
Alarm Plan Check3/24/2020 3/24/2020 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  3/24/2020 DONE
As built # 2. Minimum $65 review fee due.
Plan resubmittals received  3/2/2020 DONE
INSP-Final Inspection1/10/20201/13/20201/13/2020AFAIL
DetailsJim Page
Overspaced audio visual devices in electrical room area, section 10 area 90. Notated city approved draiwngs areas where candella setting was incorrect, inspection was stopped after 6 deficiencies.

Dillion Phone #: ###-####
INSP-Final Inspection1/8/20201/10/20201/10/2020ACANC
DetailsJim Page
Coordinated for 13JAN2020, cancelled due to inspection load and time required for this inspection.

Dillion Phone #: ###-####
INSP-Final Inspection12/19/201912/20/201912/20/2019PPART
DetailsJim Page
FIre alarm inspection for TCUP is complete, fire alarm system in TCUP is compliant with NFPA 72, Due to this system being included in the B51 plans, Fire Alarm Plan Examiner still needs to perform review, per conversation with Joe Bruce, Fire Section Supervisor, if fire alarm system is compliant with NFPA 72 then life fire safety inspection can be performed due to the TCUP being included on the B51 drawings. Will verify that install matches submittal during B51 inspection.

.tea cup // Dillon Phone #: ###-####
CHANGE STATUS TO (ISS)  12/19/2019 DONE
as built- no fee per Lee
Plan assigned to (Lee)12/4/2019 12/18/2019 DONE
DetailsLee G Meredith
1st review completed  12/18/2019 DONE
Alarm Plan Check12/18/2019 12/18/2019 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  12/18/2019 DONE
As built. No Fee.
Plan Modification Accepted  12/4/2019 DONE
as built
INSP-Alarm Testing10/22/201910/22/201910/22/2019AFAIL
DetailsJim Page
Started inspection in level 10, section 90 of the city approved drawings, notated 7 areas that need corrected where candella settings due not match what was submitted as well as a/v devices that have been added that are not on city approved drawings, inspection stopped due to defecincies noted.

Requesting for 10/22 AM
INSP-Alarm Testing10/21/201910/21/201910/21/2019PCANC
DetailsTroy Cobbley
To be rescheduled per paul ###-####
INSP-Final Inspection10/8/201910/9/201910/9/2019ACANC
DetailsJim Page
Dillon Phone #: ###-####
INSP-Alarm Testing11/7/201711/8/201711/8/2017PPART
DetailsJim Page
Fire alarm testing/inspection for TCUP building complete.
INSP-Conference10/23/201710/23/201710/23/2017PDONE
DetailsJim Page
Discuss requirements for passenger elevator control room/and shaft.
Currently the elevator controller is in the shaft space. There are no walls or hard lid that separate the controller and the shaft. Top of the shaft is 60ft above controller. Device maintenance is a concern.
Tribal Fire also questions the location of the sprinkler heads needed.


Issue is deferred to fire alarm system design and plan review to provide a solution.
INSP-Alarm Testing10/10/201710/11/201710/11/2017ADONE
DetailsJim Page
Audio visual notification for Building 51.2 sections complete. Fire riser monitoring for area's associated with building 51.2 complete.
INSP-Alarm Testing7/11/20177/12/20177/12/2017PDONE
DetailsJim Page
Alarm testing for deluge system associated with this permit complete.
INSP-Alarm Testing6/29/20176/30/20176/30/2017PPART
DetailsJim Page
Fire alarm testing for fire sprinkler risers protecting TCO requested area complete, audio visual device testing for TCO requested area complete to include clean room area.
INSP-Alarm Testing6/27/20176/29/20176/29/2017PCANC
DetailsJim Page
Inspection request cancelled per conversation with Toby Phone #: ###-#### Inspection requested will be rescheduled.
Meeting  6/8/2017 DONE
Met on site with Paul, Ron Johnson and several contractors involved in the project to discuss control requirements of the B50 and B51 link deluge systems. It was agreed that current code requiring listed releasing components and supervised service disconnects will be used.
Alarm Plan Check6/8/2017 6/8/2017 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  6/8/2017 DONE
Plans approved, as noted, with review comments and requirements.
Permit Ready to Issue  6/8/2017 DONE
Issue and Print Permit  6/8/2017 DONE
(F) Reprint permit  6/8/2017 DONE
Inspection Record Card- Fire6/8/2017 6/8/2017 DONE
DetailsChristina Prado
Miscellaneous action  6/5/2017 DONE
Voltage drop and battery calcs received. Numerous errors found.
Telephone call  6/2/2017 DONE
Discussed calculation errors with Paul Marcolina. He will have Curtis call to discuss how they would like to proceed.
Plan resubmittals received  5/25/2017 DONE
Miscellaneous action  5/25/2017 DONE
Updated notification voltage drop calculations missing. Emailed Paul and asked him to send at his convenience.
Miscellaneous action  5/19/2017 DONE
Paul appears to have uploaded the resubmittal into FIR17-00221. (Modular Office project). Informed him via email to verify and make corrections.
Miscellaneous action  4/21/2017 DONE
Dan Krishnek of Power Plus Electric (fire alarm installing contractor) emailed requesting copies of the floor plan mark ups for corrections. I informed him that Paul Marcolina should be able to provide these, since he is the applicant.
Telephone call  4/20/2017 DONE
Paul Marcolina called to indicate he was having problems accessing the drawings with mark ups. I had him call Rita for assistance.
Miscellaneous action  4/19/2017 DONE
1st review comments sent to Paul Marcolina.
Application received  4/14/2017 DONE
Application submitted via PDS Online on Apr 14 2017 12:01PM
Plan assigned to (Lee)4/14/2017 4/14/2017 DONE
DetailsLee G Meredith
1st review completed  4/14/2017 FAIL
See review comments