INSP-Final Inspection | 10/10/2017 | 10/12/2017 | 10/12/2017 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled.
|
INSP-Final Inspection | 9/27/2017 | 9/28/2017 | 9/28/2017 | P | FAIL |
Troy Cobbley
|
|
|
The system functioned except for when testing the link/cable under the large hood. Per Ken the cable hung up on grease. This portion will need to be re-tested.
|
INSP-Final Inspection | 9/12/2017 | 9/19/2017 | 9/18/2017 | A | CANC |
Troy Cobbley
|
|
|
We will be set up for you, Troy, at 7 AM, if that''s at all possible for you. The kitchen hood lights have been wired to the shunt. Your contact will be Ken Danes. Phone #: ###-#### >> Inspection requested via web by Connie Danes Inspection cancelled from web by: Connie Danes
|
INSP-Final Inspection | 8/1/2017 | 8/3/2017 | 8/3/2017 | A | FAIL |
Troy Cobbley
|
|
|
Provide functional trip test to verify electrical and gas shut off that utilizes test line and remote pull station, lights under the hood need to shut off, provide test report.
|
INSP-Final Inspection | 7/28/2017 | 8/2/2017 | 8/1/2017 | A | CANC |
Troy Cobbley
|
|
|
Technician on site will be Ken Danes. This NEEDS to be done first thing in the morning, 7 - 7:30 preferably, since Red Lobster starts cooking under this kitchen hood around 8-8:30 and doesn''t finish until 10 PM. Phone #: ###-#### >> Inspection requested via web by Connie Danes Inspection cancelled from web by: Connie Danes
|
Issue permit | | | 7/13/2017 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 5/12/2017 | | DONE |
|
|
|
This permit was created on the web by Ken Danes
|