INSP-Final Inspection | 8/2/2017 | 8/4/2017 | 8/4/2017 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
Plan assigned to (Lee) | 5/26/2017 | | 5/26/2017 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 5/26/2017 | | PASS |
|
|
|
|
Alarm Plan Check | 5/26/2017 | | 5/26/2017 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 5/26/2017 | | DONE |
|
|
|
Plans approved with review comments and several requirements.
|
Permit Ready to Issue | | | 5/26/2017 | | DONE |
|
|
|
|
Issue and Print Permit | | | 5/26/2017 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 5/26/2017 | | 5/26/2017 | | DONE |
Tisha Gallop
|
|
|
|
Telephone call | | | 5/26/2017 | | DONE |
|
|
|
Jeremy Berg called to question the requirement of the paging capability at the annunciator. FACP is located less than 10 feet from the entry in an unsecured office so I told him that if adequate signage is clearly posted that indicates the location of the fire alarm page mic that it would be adequate. Page mic at annunciator will not be required.
|
Application received | | | 5/24/2017 | | DONE |
|
|
|
Application submitted via PDS Online on May 24 2017 2:49PM
|