INSP-Final Inspection | 8/28/2018 | 8/29/2018 | 8/29/2018 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled.
Rafe Phone #: ###-####
|
INSP-Final Inspection | 8/2/2018 | 8/3/2018 | 8/3/2018 | P | CANC |
Troy Cobbley
|
|
|
Rafe Phone #: ###-####
|
Miscellaneous action | | | 8/3/2018 | | DONE |
|
|
|
As built drawings received and approved. Uploaded to eplanreview.
|
INSP-Final Inspection | 4/30/2018 | 5/1/2018 | 5/1/2018 | A | FAIL |
Troy Cobbley
|
|
|
Provide as-builts with the candella changes and the revised zones. Provide adjustment for the tamper switches, provide supervisory signal to the monitoring agency.
6:30 am inspection // Rase Phone #: ###-####
|
INSP-Final Inspection | 4/19/2018 | 4/20/2018 | 4/20/2018 | A | FAIL |
Troy Cobbley
|
|
|
See the city approved plans for corrections needed. No actual testing performed.
Rafe Phone #: ###-####
|
INSP-Final Inspection | 4/10/2018 | 4/12/2018 | 4/12/2018 | P | CANC |
Troy Cobbley
|
|
|
Rafe Phone #: ###-####
|
Plan Modification Accepted | | | 3/20/2018 | | DONE |
|
|
|
|
Alarm Plan Check | 3/20/2018 | | 3/20/2018 | | PASS |
Lee G Meredith
|
|
|
Plans approved shown and noted. Approval is subject to inspector's review of corrections previously noted in activity on 2-15-18.
|
PLANS TAKEN FRONT DESK ALARM | | | 3/20/2018 | | DONE |
|
|
|
Plans approved as noted with review comments.
|
Permit Ready to Issue | | | 3/20/2018 | | DONE |
|
|
|
Plan Mod Approved
DO NOT REISSUE
|
Issue and Print Permit | | | 3/20/2018 | | DONE |
|
|
|
|
INSP-Final Inspection | 2/5/2018 | 2/15/2018 | 2/15/2018 | P | FAIL |
Troy Cobbley
|
|
|
For todays inspection we did a walk through for the placement of the notification devices. No actual testing was performed due to numerous corrections needed and no small documents available on site. I noted the manual pull stations are not mounted at the correct heights and one manual pull station has not been relocated yet as shown on the plans. Several strobes are overspaced and there are many locations where additional notification devices will be required. These locations include rooms marked as "offices" but are actually set up with functioning medical equipment. Also the floor plan/wall layout does not match in all locations. It appears plan modifications are required prior to the next inspection.
Rafe Phone #: ###-####
|
1st review completed | | | 5/30/2017 | | PASS |
|
|
|
|
Alarm Plan Check | 5/30/2017 | | 5/30/2017 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 5/30/2017 | | DONE |
|
|
|
Plans approved with review comments and drawing notes.
|
Permit Ready to Issue | | | 5/30/2017 | | DONE |
|
|
|
|
Issue and Print Permit | | | 5/30/2017 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 5/30/2017 | | 5/30/2017 | | DONE |
Tisha Gallop
|
|
|
|
Application received | | | 5/26/2017 | | DONE |
|
|
|
Application submitted via PDS Online on May 26 2017 8:23AM
|
Plan assigned to (Lee) | 5/26/2017 | | 5/26/2017 | | DONE |
Lee G Meredith
|
|
|
|
Miscellaneous action | | | 5/26/2017 | | DONE |
|
|
|
Asked Dante for more information on the east basement dwelling units. there is no coverage shown. Informed him that it appears they will need low frequency sounders and strobes. Dante responded to say that those rooms are actually confirmed as offices.
|