Permit Information
Permit NumberFIR17-00259
StatusFinaled
Name SIMPLEX GRINNELL
Site Address 777 N RAYMOND ST
Project NameFAMILY MED RESIDENCY OF IDAHO
Customer Number 
ePlanReviewYes
Description
Family Medicine Residency of Idaho job is to remove existing Simplex 2001 FACP and replace with new Simplex 4007ES FACP. Reconnect existing dialer, zone initiation circuits, door holder circuit and auxiliary power circuits to new FACP. Extend a new IDNET SLC circuit to new initiation devices and new NAC circuits to new notification devices as shown on the plans. Existing notification devices to be removed and covered. Existing NAC circuit to be removed. This work is not associated with a building permit.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/28/20188/29/20188/29/2018APASS
DetailsTroy Cobbley
Permit finaled.


Rafe Phone #: ###-####
INSP-Final Inspection8/2/20188/3/20188/3/2018PCANC
DetailsTroy Cobbley
Rafe Phone #: ###-####
Miscellaneous action  8/3/2018 DONE
As built drawings received and approved. Uploaded to eplanreview.
INSP-Final Inspection4/30/20185/1/20185/1/2018AFAIL
DetailsTroy Cobbley
Provide as-builts with the candella changes and the revised zones. Provide adjustment for the tamper switches, provide supervisory signal to the monitoring agency.

6:30 am inspection // Rase Phone #: ###-####
INSP-Final Inspection4/19/20184/20/20184/20/2018AFAIL
DetailsTroy Cobbley
See the city approved plans for corrections needed. No actual testing performed.

Rafe Phone #: ###-####
INSP-Final Inspection4/10/20184/12/20184/12/2018PCANC
DetailsTroy Cobbley
Rafe Phone #: ###-####
Plan Modification Accepted  3/20/2018 DONE
Alarm Plan Check3/20/2018 3/20/2018 PASS
DetailsLee G Meredith
Plans approved shown and noted. Approval is subject to inspector's review of corrections previously noted in activity on 2-15-18.
PLANS TAKEN FRONT DESK ALARM  3/20/2018 DONE
Plans approved as noted with review comments.
Permit Ready to Issue  3/20/2018 DONE
Plan Mod Approved
DO NOT REISSUE
Issue and Print Permit  3/20/2018 DONE
INSP-Final Inspection2/5/20182/15/20182/15/2018PFAIL
DetailsTroy Cobbley
For todays inspection we did a walk through for the placement of the notification devices. No actual testing was performed due to numerous corrections needed and no small documents available on site. I noted the manual pull stations are not mounted at the correct heights and one manual pull station has not been relocated yet as shown on the plans. Several strobes are overspaced and there are many locations where additional notification devices will be required. These locations include rooms marked as "offices" but are actually set up with functioning medical equipment. Also the floor plan/wall layout does not match in all locations. It appears plan modifications are required prior to the next inspection.

Rafe Phone #: ###-####
1st review completed  5/30/2017 PASS
Alarm Plan Check5/30/2017 5/30/2017 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  5/30/2017 DONE
Plans approved with review comments and drawing notes.
Permit Ready to Issue  5/30/2017 DONE
Issue and Print Permit  5/30/2017 DONE
Inspection Record Card- Fire5/30/2017 5/30/2017 DONE
DetailsTisha Gallop
Application received  5/26/2017 DONE
Application submitted via PDS Online on May 26 2017 8:23AM
Plan assigned to (Lee)5/26/2017 5/26/2017 DONE
DetailsLee G Meredith
Miscellaneous action  5/26/2017 DONE
Asked Dante for more information on the east basement dwelling units. there is no coverage shown. Informed him that it appears they will need low frequency sounders and strobes. Dante responded to say that those rooms are actually confirmed as offices.