Permit Information
Permit NumberFIR17-00301
StatusFinaled
Name TRIBAL FIRE SYSTEMS
Site Address 8000 S FEDERAL WAY
Project NameMicron Bldg 51
Customer Number 
ePlanReviewYes
Description
[Micron Building 51 - System 20-9 - C24074]
The fire sprinkler scope of work consists of part of the level 20. The system is designed as a
4”x 4” x 2½” grid with a 6” feed main. There are two side feed areas.

• The underground is under permit FIR16-00701
• See addendum for graphic scope of work

[BLD16-03440]
For the construction of a new one story building with a basement for a fabrication and R&D facility to include related site work. The building includes a 157,037 sq. ft. basement, a 170,997 sq. ft. first story and a 33,638 sq. ft. equipment platform. This building is fully fire sprinklered and alarmed for H occupancy. CDM
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/12/20198/13/20198/13/2019APASS
DetailsJim Page
Final inspection for scope of work has been completed. Catwalks have been added that were outside the scope of work, fire sprinkler coverage will be required for life fire safety to be completed, a seperate permit will be required for obstruction coverage.

Clarence Phone #: ###-#### Inspection requested via web by Jessia Maxwell
INSP-Sprinkler Rough-in/Hydro8/13/20198/13/20198/13/2019ADONE
DetailsJim Page
Hydrostatic test for this system has been witnessed, no pressure loss was observed.
INSP-Sprinkler Rough-in8/13/20198/13/20198/13/2019APASS
DetailsJim Page
Rough in inspection for this system has been completed.
Fees Due Hold2/28/2018 3/8/2018 DONE
DetailsBrittany Hill
Fees Due Hold1/23/2018 2/27/2018 DONE
DetailsBrittany Hill
Issue and Print Permit  1/22/2018 DONE
DetailsChristina Prado
MIcron project - will be paid by Micron during monthly processing
Sprinkler Plan Check1/19/2018 1/19/2018 PASS
DetailsTim Frost
Please, see attached comments.
PLANS/APPL TAKEN TO FRONT DESK  1/19/2018 DONE
DetailsTim Frost
Permit Ready to Issue  1/19/2018 DONE
Telephone call  1/3/2018 DONE
Spoke with the Assitant Fire Marshal. Explained, the owner would not provide the quanities or type of commodities being used and stored ( solvents, water reactive, slurry and aqueous ) The owner said it was proprietary information.

I explained the design calls for a wet pipe sprinklers protecting a water reactive area. I also explained I had tried to contact the owner in regards to this matter and the phone call was never returned. I asked him to follow up with the owner and let me know how he would like me to proceed. I suggested the owner should provide a letter from their insurance underwrited (FM) stating the area has adequate protection.
Miscellaneous action  1/3/2018 PEND
Waiting on Paul to contact Ron in regards to water reactive area and quantities and types of chemicals.
Miscellaneous action  1/3/2018 PEND
Waiting on Clarence to tell me the wall rating. If it is not 90 min then additional flow is required in remote area 1
Intake Approval  12/20/2017 PASS
Plan assigned to (Tim)12/20/2017 12/20/2017 DONE
DetailsTim Frost
Sprinkler Plan Check12/20/2017 12/20/2017 FAIL
DetailsTim Frost
Please, see attached comments.
1st review completed  12/20/2017 FAIL
DetailsTim Frost
Miscellaneous action  12/20/2017 DONE
DetailsTim Frost
Emailed contractor in regards to failed review.
Application received  6/19/2017 DONE
Application submitted via PDS Online on Jun 19 2017 6:43AM