INSP-Final Inspection | 10/20/2017 | 10/20/2017 | 10/20/2017 | P | PASS |
Jim Page
|
|
|
Final fire sprinkler inspection passed/complete.
|
Fees Due Hold | 10/19/2017 | 10/19/2017 | 10/19/2017 | | PASS |
|
|
|
|
INSP-Final Inspection | 10/17/2017 | 10/18/2017 | 10/18/2017 | P | FAIL |
Jim Page
|
|
|
Flow switch would not activate on waterflow.
|
INSP-Final Inspection | 10/13/2017 | 10/13/2017 | 10/13/2017 | P | CANC |
Jim Page
|
|
|
Final inspection request will be rescheduled for a later date per conversation with Jake, phone number ###-####.
|
INSP-Final Inspection | 10/4/2017 | 10/6/2017 | 10/6/2017 | A | FAIL |
Jim Page
|
|
|
Isolation valve for fire sprinkler system is required per fire sprinkler permit review.
|
INSP-Sprinkler Rough-in | 7/18/2017 | 7/19/2017 | 7/19/2017 | P | PASS |
Jim Page
|
|
|
Rough to cover inspection for overhead fire sprinkler piping/tenting complete, approved for cover.
|
INSP-Sprinkler Rough-in | 7/17/2017 | 7/18/2017 | 7/18/2017 | A | FAIL |
Jim Page
|
|
|
Multiple area's where piping is exposed to attic space, piping not covered with plastic sheeting, pocket will not be maintained between sheetrock and fire sprinkler piping, cover is not approved.
|
INSP-Sprinkler Rough-in/Hydro | 7/9/2017 | 7/10/2017 | 7/10/2017 | P | PART |
Jim Page
|
|
|
Hydrostatic test complete for overhead fire sprinkler piping. Rough in inspection for overhead fire sprinkler piping complete, piping between conditioned area's approved for cover, fire sprinkler piping located in attic spaces cannot be covered until insulation/tenting has been installed over the top of the fire sprinkler piping and tenting passed inspection.
|
INSP-Sprinkler Rough-in/Hydro | 7/6/2017 | 7/6/2017 | 7/6/2017 | P | FAIL |
Jim Page
|
|
|
Fire sprinkler dead needs to be added or relocated to cover under stairs as shown on approved drawings. Fire sprinkler head in the southeast bedroom needs to be relocated to cover shadow area above closet area.
|
INSP-Sprinkler Rough-in/Hydro | 6/30/2017 | 7/6/2017 | 7/6/2017 | A | CANC |
Jim Page
|
|
|
Please call Jake when heading out, thanks! Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello Inspection cancelled from web by: Anthony Minichiello
|
Issue and Print Permit | | | 6/23/2017 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 6/23/2017 | | 6/23/2017 | | DONE |
Tisha Gallop
|
|
|
|
Intake Approval | | | 6/22/2017 | | PASS |
|
|
|
|
Plan assigned to (Tim) | 6/22/2017 | | 6/22/2017 | | DONE |
Tim Frost
|
|
|
|
Sprinkler Plan Check | 6/22/2017 | | 6/22/2017 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
|
1st review completed | | | 6/22/2017 | | PASS |
Tim Frost
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/22/2017 | | DONE |
Tim Frost
|
|
|
|
Application received | | | 6/20/2017 | | DONE |
|
|
|
Application submitted via PDS Online on Jun 20 2017 12:47PM
|