INSP-Final Inspection | 8/17/2017 | 8/17/2017 | 8/17/2017 | A | PASS |
Jim Page
|
|
|
Area of work does have active fire alarms throughout tenant space, audio alarms do not have 3 temporal throughout space. Contractor is working with building manager/property owners to upgrade fire alarm system upgrade to address notification issues. Final fire alarm inspection for this area of work complete, any other future work throughout building that occurs and fire alarm issues are not resloved will result in an inspection failure.
|
1st review completed | | | 7/3/2017 | | PASS |
|
|
|
Approved as noted on drawings and review comments.
|
Alarm Plan Check | 7/3/2017 | | 7/3/2017 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 7/3/2017 | | DONE |
|
|
|
Plans approved with review comments and notation on drawings.
|
Permit Ready to Issue | | | 7/3/2017 | | DONE |
|
|
|
|
Issue and Print Permit | | | 7/3/2017 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 7/3/2017 | | 7/3/2017 | | DONE |
Brittany Hill
|
|
|
|
Plan assigned to (Lee) | 6/30/2017 | | 6/30/2017 | | DONE |
Lee G Meredith
|
|
|
|
Miscellaneous action | | | 6/30/2017 | | DONE |
|
|
|
Emailed Dante to inform him that a notifiaction panel cannot be activated by a notification circuit that has devices on it per 2012 NFPA 72.
|
Application received | | | 6/29/2017 | | DONE |
|
|
|
Application submitted via PDS Online on Jun 29 2017 4:05PM
|