INSP-Final Inspection | 4/10/2018 | 4/11/2018 | 4/11/2018 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
Call prior to going Phone #: 2089411846 >> Inspection requested via mobile web by SVC Brian A
|
Miscellaneous action | | | 3/22/2018 | | DONE |
|
|
|
seperated as built drawings uploaded and approved.
|
(F) Reprint permit | | | 3/22/2018 | | DONE |
|
|
|
|
(F) Reprint permit | | | 3/22/2018 | | DONE |
|
|
|
|
Miscellaneous action | | | 3/22/2018 | | DONE |
|
|
|
as per Lee M no additional fees due for the as built
|
Miscellaneous action | | | 3/21/2018 | | DONE |
|
|
|
UPDATED as built drawings received. Returned to Shane since they were grouped together as a single file.Workflow was reopenend and I send Shane an email requesting he upload files after he breaks them apart.
|
INSP-Final Inspection | 3/8/2018 | 3/9/2018 | 3/9/2018 | A | FAIL |
Troy Cobbley
|
|
|
The double doors did not release from the mag/hold opens upon alarm and a new single door that is "Delayed Egress Lock" was not connected to the fire alarm system for release as required by IFC 1008.1.9.7
|
Miscellaneous action | | | 3/9/2018 | | DONE |
|
|
|
As built drawings received from Shane.
|
INSP-Alarm Testing | 3/2/2018 | 3/2/2018 | 3/2/2018 | A | CANC |
Troy Cobbley
|
|
|
Call prior to going Phone #: 2089411846 >> Inspection requested via mobile web by SVC Brian A Inspection cancelled via mobile web on Friday, March 02, 2018.
|
INSP-Alarm Testing | 12/19/2017 | 12/20/2017 | 12/20/2017 | A | DONE |
Troy Cobbley
|
|
|
The fire alarm is complete in Rooms 209 and 210
As early as possible Phone #: 2089411846 >> Inspection requested via mobile web by SVC Brian A
|
INSP-Alarm Testing | 12/19/2017 | 12/19/2017 | 12/19/2017 | P | CANC |
Troy Cobbley
|
|
|
Call prior to going Phone #: 2089411846 >> Inspection requested via mobile web by SVC Brian A Inspection cancelled via mobile web on Tuesday, December 19, 2017.
|
INSP-Alarm Testing | 11/16/2017 | 11/17/2017 | 11/17/2017 | A | PART |
Troy Cobbley
|
|
|
Work is complete in the two Anesthsia Rooms.
|
Permit Ready to Issue | | | 7/11/2017 | | DONE |
|
|
|
|
Issue and Print Permit | | | 7/11/2017 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 7/11/2017 | | 7/11/2017 | | DONE |
Christina Prado
|
|
|
|
Application received | | | 7/10/2017 | | DONE |
|
|
|
Application submitted via PDS Online on Jul 10 2017 11:36AM
|
Plan assigned to (Lee) | 7/10/2017 | | 7/10/2017 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 7/10/2017 | | PASS |
|
|
|
|
Alarm Plan Check | 7/10/2017 | | 7/10/2017 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 7/10/2017 | | DONE |
|
|
|
Plans approved with eview comments.
|