Permit Information
Permit NumberFIR17-00431
StatusFinaled
Name SOUND SECURITY
Site Address 7997 W FRANKLIN RD
Project NameLong Horn Steak House
Customer Number 
ePlanReviewYes
Description
Provide a full manual fire alarm system, monitor kitchen hood and duct detectors. Submittal is actually prepared by Stanley Convergent Security Solutions, Inc in Fishers, IN. This work is associated with building permit BLD17-00729.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/7/201712/8/201712/8/2017APASS
DetailsTroy Cobbley
Permit finaled

Phone #: ###-#### Inspection requested via web by Kyle Burgess
INSP-Final Inspection12/6/201712/7/201712/7/2017PFAIL
DetailsTroy Cobbley
All items tested ok except one of the three duct smoke detectors needs to be relocated to the narrow side of the rectangular duct and provided with the correct sample tube and re-tested.
Issue and Print Permit  12/6/2017 DONE
Miscellaneous action  12/5/2017 DONE
Mary requested workflow be opened for a plan modification.
Plan Modification Accepted  12/5/2017 DONE
Adding romm temperature sensors that will be monitored by the fire alarm system for sprinklers above ceiling.
Alarm Plan Check12/5/2017 12/5/2017 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  12/5/2017 DONE
Plans approved. No additional review comments.
Permit Ready to Issue  12/5/2017 DONE
INSP-Final Inspection11/29/201711/30/201711/30/2017PFAIL
DetailsTroy Cobbley
Missing all small documents, communication does not match plans, appears atleast two strobes need to be added. No testing performed.
Miscellaneous action  11/14/2017 DONE
Mary emailed syaing the FACP and NAC panels have been relocated to the managers office. Associated smoke detector has been relocated as well. I told her that since there is already a remote annunciator, relocation of the panels did not require a plan mod. Also, duct detectors are being supplied by the fire alarm contractor instead of the mechanical. Product data is to be provided with as built drawings prior to acceptance. Plan mod not required since notification and loads are not affected.
Miscellaneous action  11/14/2017 DONE
As build drawings received and filed in eplan review.
Issue and Print Permit  8/15/2017 DONE
Inspection Record Card- Fire8/15/2017 8/15/2017 DONE
DetailsBrittany Hill
Plan assigned to (Lee)8/14/2017 8/14/2017 DONE
DetailsLee G Meredith
1st review completed  8/14/2017 DONE
Failed pre-screen review. Drawings all combined as a single file. Emailed Mary to let her know individual drawing files are required. She respoinded to say she will resubmit.
Miscellaneous action  8/14/2017 DONE
Received drawings seperated into individual files. Scale graph is not right. Requested correction.
Alarm Plan Check8/14/2017 8/14/2017 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  8/14/2017 DONE
Plans approved with review comments.
Permit Ready to Issue  8/14/2017 DONE
Application received  8/9/2017 DONE
Application submitted via PDS Online on Aug 9 2017 12:06PM