Permit Information
Permit NumberFIR17-00444
StatusFinaled
Name FIRE SENTRY SYSTEMS
Site Address 12754 W LASALLE ST
Project NameSEL Notification Upgrade
Customer Number 
ePlanReviewYes
Description
Current facility has no audible or visual notification. Upgrade will cover all common areas and corridors with A/V notification. Appliances to be powered by a new 6 amp power extender panel triggered by the existing FACP NAC circuit. Existing FACP is a basic riser monitor. During the upgrade, a pull station will be added at the receptionist's desk for manual activation of system.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/20/20179/22/20179/22/2017APASS
DetailsJim Page
As-builts are complete, final fire alarm inspection passed/complete.
Plan Modification Accepted  9/20/2017 DONE
CHANGE STATUS TO (REV)  9/20/2017 DONE
Changed to review status due to plan modification submittal.
Alarm Plan Check9/20/2017 9/20/2017 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  9/20/2017 DONE
Plan modification approved. No additional review comments.
Permit Ready to Issue  9/20/2017 DONE
DetailsChristina Prado
Plan Mod - All requirements met
Issue and Print Permit  9/20/2017 DONE
Miscellaneous action  9/19/2017 DONE
John requested the workflow be re-opened for a plan modification that will add strobes to multi tenant offices.
INSP-Final Inspection9/13/20179/15/20179/15/2017AFAIL
DetailsTroy Cobbley
Not all items tested today. I verified the battery trouble and output circuit trouble from the NAC panel. I noted many of the 15cd strobes are mounted above 10'. Since candella will be changes as-builts will need to be provided to myself and plan review showing the changes. John Phone #: ###-####
INSP-Final Inspection9/13/20179/13/20179/13/2017PCANC
DetailsJim Page
Inspection request cancelled per conversation with John Howard Phone #: ###-####, Inspection will be rescheduled for a later date.
Plan assigned to (Lee)8/17/2017 8/17/2017 DONE
DetailsLee G Meredith
1st review completed  8/17/2017 PASS
Alarm Plan Check8/17/2017 8/17/2017 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  8/17/2017 DONE
Plans approved with review comments.
Permit Ready to Issue  8/17/2017 DONE
Issue and Print Permit  8/17/2017 DONE
Inspection Record Card- Fire8/17/2017 8/17/2017 DONE
DetailsBrittany Hill
Application received  8/16/2017 DONE
Application submitted via PDS Online on Aug 16 2017 4:56PM