INSP-Final Inspection | 6/25/2018 | 6/26/2018 | 6/26/2018 | P | PASS |
Jim Page
|
|
|
Final fire alarm inspection complete.
Travis Phone #: ###-####
|
INSP-Final Inspection | 6/22/2018 | 6/25/2018 | 6/25/2018 | P | FAIL |
Jim Page
|
|
|
Sounder bases in rooms would not stay in alarm during general alarm, sounder bases need to keep sounding during general alarm.
Travis Phone #: ###-####
|
INSP-Final Inspection | 6/21/2018 | 6/22/2018 | 6/22/2018 | P | PART |
Jim Page
|
|
|
Inspection complete for room notification on levels 2 through 5. Fire sprinkler tampers and flow switches complete for levels 1 through 5, point description for standpipe control valves in riser room and level 2 roof top hose valve will be changed to discussed discription. Hood suppression monitoring is complete. Level 1 notification and common area notification and elevator recall to be tested at a later date. Monitoring needs to be verified prior to fire alarm permit being finaled.
Travis Phone #: ###-####
|
Issue and Print Permit | | | 10/6/2017 | | DONE |
|
|
|
|
Plan resubmittals received | | | 10/2/2017 | | DONE |
|
|
|
|
Alarm Plan Check | 10/2/2017 | | 10/2/2017 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 10/2/2017 | | DONE |
|
|
|
Plans approved with review comments and drawing notation.
|
Miscellaneous action | | | 10/2/2017 | | DONE |
|
|
|
Permit was submited under 301 S 13th st. As per Lee correct address is 348 s 13th
|
Permit Ready to Issue | | | 10/2/2017 | | DONE |
|
|
|
all met
|
Miscellaneous action | | | 9/20/2017 | | DONE |
|
|
|
Emailed Steve requesting product data for low frequency horns that were not included in the resubmittal.
|
Plan resubmittals received | | | 9/19/2017 | | DONE |
|
|
|
|
Plan assigned to (Lee) | 9/12/2017 | | 9/12/2017 | | DONE |
Lee G Meredith
|
|
|
|
Miscellaneous action | | | 9/12/2017 | | DONE |
|
|
|
Requested a scale graph be added to the floor plans. Steve, emailed the updates as requested.
|
1st review completed | | | 9/12/2017 | | FAIL |
|
|
|
Several areas missing notification. Hearing impaired rooms do not have visible notification.
|
Miscellaneous action | | | 9/12/2017 | | DONE |
|
|
|
Discussed reasons for return of drawings for corrections with Steve. Emailed a copy of the review comments.
|
Application received | | | 8/23/2017 | | DONE |
|
|
|
Application submitted via PDS Online on Aug 23 2017 9:11AM
|