Information based on query as of Wednesday, July 24, 2024.
Permit Information
Permit NumberFIR17-00474
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 519 N 9TH ST
Project NameBoise H.S. Gym & Arts Reno.
Customer Number 
ePlanReviewYes
Description
[Boise High School Gym & Arts Renovations]
The fire sprinkler scope of work consists of complete renovation of the existing Gym and Performing Arts building. The existing building has three levels. Also, there is a new two story addition on the west side of the building. The new addition supplies the existing upper-level system cross main. The layout of the upper floor of the new addition is tree type with 4” main and 1½” lines. The bottom level of the new addition has a grid type layout with 4” mains and 1½” lines.

[BLD17-01000]
The fire sprinkler system is used for building area increase and for fire area. The entire single story West classroom portion of this building will be demolished. Within the Gym portion of this building on the 1st story the elevated wood framed stage, two structural columns, the locker rooms and the mezzanine floors above, the exterior windows, exterior doors, and the wood bleachers will be demolished. The East mezzanine will be maintained.

To construct a new 28,186 square foot classroom addition on the West side of the existing Gym building (9,189 square feet basement, 9,778 square feet 1st story, and 9,219 square feet 2nd story). For the new portion of this building, work is to include concrete footings; concrete foundations; basement concrete slab on grade; concrete and steel pan deck floors supported by steel columns, beams, and joists; masonry exterior walls; masonry exterior veneer; steel roof system with insulation installed on top of the roof deck; single ply roofing membrane; steel awnings; three coat exterior plaster; exterior concrete landings, stairs, and ramps with handrails and guards for this addition and for the building to the North; new concrete sidewalks; an elevator and 1-hr elevator shaft; interior walls; 4 toilet rooms accessible to the disabled; an assisted-use toilet room accessible to the disabled; interior stairways; doors; windows; and finishes.

To remodel an existing 31,341 square foot Gym building (12,048 square feet basement, 16,741 square feet 1st story, and 2,552 square feet 1st story mezzanine). For the Gym, work is to include structural modifications to the roof structure (i.e. new trusses, new truss braces, diaphragm cords, perimeter diaphragm nailing, parapet braces, etc. to replace removed columns and beams); interior steel columns and beams at exterior walls to resist out-of-plane lateral loads; floor structures at sunken floors; steel headers and jams at new masonry and concrete wall openings; wall furring; insulation installed on top of the roof deck; new single ply roofing membrane; new landings and bollards at exterior doors that swing into the alley; exterior brick infills at window openings in the alley wall; exterior brick repairs; handrails at the existing East exterior stairways; new interior stairways; a new 1-hr stairway enclosure; an elevator and elevator shaft; new exterior doors and aluminum windows; extending wood flooring for the playing court; bleachers; two toilet rooms accessible to the disabled on the 1st story; basement locker rooms with accessible showers, toilets, urinals, and lockers; interior walls; millwork; and finishes.

Special Inspection is required for soils, concrete, masonry, steel (including welding and bolting), and anchors post installed in hardened concrete and brick. The design for the tiered platform within the Micro Theater is a deferred submittal item. The work is required to comply with the approved drawings, with the structural design, with the plan review report, and with all applicable codes and ordinances. The fire sprinkler system is required to comply with NFPA 13 and the fire alarm system with an emergency voice/alarm communication system is required to comply with NFPA 72 as regulated by the Fire Department. Separate fire sprinkler permits and fire alarm permits shall be obtained prior to beginning any modification or installation work on such systems. **CJW**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/18/20196/19/20196/19/2019APASS
DetailsJim Page
Final fire sprinkler inspection is complete.

Mark Jensen is the contact. This inspection has already been done, they just wanted a paper trail. Call the contact with further questions. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Final Inspection4/16/20194/18/20194/18/2019APART
DetailsJim Page
Final fire sprinkler inspection for TCO Phase 2 complete.

Mark Jensen is the contact. This final is only for the east end. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Final Inspection1/28/20191/29/20191/29/2019APART
DetailsJim Page
Fire sprinkler inspection for TCO phase 1 complete.

Contact is Mark Jensen.
Thank you for your help! Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Final Inspection1/28/20191/30/20191/28/2019ACANC
DetailsJim Page
The contact is Todd Ketterling. Thank you for your help! Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
INSP-Final Inspection1/25/20191/28/20191/28/2019ACANC
DetailsJim Page
Cancelled per conversation with GC, inspection will be rescheduled for a later date.

Mark Jensen is the contact. Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Final Inspection1/15/20191/16/20191/16/2019AFAIL
DetailsJim Page
Radius ceiling tiles hang down 7 inches from the ceiling, tile locations to sprinkler heads are not code compliant based on tables 8.6.5.1.2 for standard spray sprinklers and table 8.8.5.1.2 for the extended coverage heads per NFPA13. No other items were inspected.

Mark Jensen is the contact. Thank you! Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Sprinkler Rough-in/Hydro1/11/20191/14/20191/14/2019PDONE
DetailsJim Page
Hydrostatic test for overehad fire sprinkler piping witnessed, no pressure loss observed.

Hydrostatic test. Jeff Chaney is the contact. Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Sprinkler Rough-in/Hydro1/11/20191/11/20191/11/2019PCANC
DetailsTroy Cobbley
Cancel per Jeff Chaney. Please call 30 minutes before inspection. Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Supply line flush1/7/20191/8/20191/8/2019ADONE
DetailsJim Page
Underground main line flush complete.

Jeff Chaney is the contact. Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Sprinkler Rough-in/Hydro1/4/20191/7/20191/7/2019ADONE
DetailsJim Page
Undergorund supply hydrostatic test witnessed, no pressure loss observed.

Jeff Chaney is the contact. Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Supply line flush1/4/20191/7/20191/7/2019PCANC
DetailsJim Page
Inspection rescheduled per conversation with point of contact, this request is cancelled.

Jeff Chaney is the contact. Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Sprinkler Rough-in12/12/201812/13/201812/13/2018APART
DetailsJim Page
Rough to cover inspection for overhead fire sprinkler piping on level 2 of addition complete, level 2 of addition approved for cover.

Mark Jensen is the contact. Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Sprinkler Rough-in12/11/201812/12/201812/12/2018ACANC
DetailsJim Page
Rescheduled per conversation with POC, inspection scheduled for 13DEC2018.

Mark Jensen is the contact. Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Sprinkler Rough-in11/20/201811/20/201811/20/2018PPART
DetailsJim Page
Partial rough to cover inspection for overhead fire sprinkler piping complete, notated city approved drawings with red ink/pink highlighter areas approved for cover.

Contact is Mark Jensen Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Sprinkler Rough-in10/15/201810/16/201810/16/2018APART
DetailsJim Page
Rough to cover inspection for fire sprinkler piping installed under the raised floor in room 720 complete, approved for cover. Addition of fire sprinkler piping under raised floor will be notated on the as-builts.

rough to cover Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Sprinkler Rough-in9/24/20189/24/20189/24/2018PPART
DetailsJim Page
Partial rough to cover inspection for overhead fire sprinkler piping complete, notated city approved drawings with green highlighter/red ink area approved for cover including date inspection was completed.

Phone #: ###-#### Inspection requested via web by Stan Beus
Sprinkler Plan Check8/2/2018 8/2/2018 PASS
DetailsTim Frost
Please, see attached comments.
Intake Approval  8/2/2018 PASS
PLANS/APPL TAKEN TO FRONT DESK  8/2/2018 DONE
DetailsTim Frost
Permit Ready to Issue  8/2/2018 DONE
CHANGE STATUS TO (ISS)  8/2/2018 DONE
As bulit no charge per Tim F
INSP-Sprinkler Rough-in7/30/20187/30/20187/30/2018PPASS
DetailsJim Page
Rough to cover inspection for underground supply complete, approved for cover.

Underground RTC Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Sprinkler Rough-in7/19/20187/20/20187/20/2018APART
DetailsJim Page
Partial rough to cover inspection complete for overhead fire sprinkler piping, notated city approved drawings with pink highlighter areas approved for cover. Drop downs and arm overs to be inspected at a later date.

Mark Jensen is the contact for this rough to cover inspection. He is hoping for an appointment in the AM. Thank you for your help. Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Sprinkler Rough-in6/25/20186/26/20186/26/2018APART
DetailsJim Page
Partial rough to cover nispection complete for overhead fire sprinkler piping, notated city approved drawings with green highlighter areas approved for cover.

Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Sprinkler Rough-in3/27/20183/28/20183/28/2018APART
DetailsJim Page
Rough to cover inspection for fire sprinkler piping and FDC piping in combustible concealed space (crawl space) on the north and south side of gym area complete, approved for cover.
Plan Modification Accepted  3/22/2018 DONE
Sprinkler Plan Check3/22/2018 3/22/2018 FAIL
DetailsTim Frost
Sprinkler Plan Check3/22/2018 3/22/2018 PASS
DetailsTim Frost
Please, see attached comments.
PLANS/APPL TAKEN TO FRONT DESK  3/22/2018 DONE
DetailsTim Frost
Permit Ready to Issue  3/22/2018 DONE
Plan Mod Approved
DO NOT REISSUE
(F) Reprint permit  3/22/2018 DONE
CHANGE STATUS TO (ISS)  3/22/2018 DONE
INSP-Sprinkler Rough-in3/20/20183/20/20183/20/2018PPART
DetailsTroy Cobbley
Todays inspection was just for the supply piping to the FDC that runs under the floor. The piping in itself is ok but the combustible concealed spaces on both side of the gym need to be addressed. I spoke to Tim Frost in plan review and he was going to follow up with the contractor. Piping can not be covered until this is resolved due to needing access to install additional piping , if required.

Mark Jensen is the contact for this rough-in for the FDC. Thank you. Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Conference3/15/20183/15/20183/15/2018PDONE
DetailsJim Page
Discussed location for FDC, FDC will be installed on the eastern side of the north wall next to emergrncy exit door instead of the east wall.
INSP-Sprinkler Rough-in3/15/20183/15/20183/15/2018PCANC
DetailsJim Page
Request is for a conference, this request is cancelled.
Sprinkler Plan Check9/11/2017 9/11/2017 PASS
DetailsTim Frost
Please, see attached comments.
PLANS/APPL TAKEN TO FRONT DESK  9/11/2017 DONE
DetailsTim Frost
Permit Ready to Issue  9/11/2017 DONE
all met
Issue and Print Permit  9/11/2017 DONE
Intake Approval  8/28/2017 PASS
Plan assigned to (Tim)8/28/2017 8/28/2017 DONE
DetailsTim Frost
Sprinkler Plan Check8/28/2017 8/28/2017 FAIL
DetailsTim Frost
1st review completed  8/28/2017 FAIL
DetailsTim Frost
Miscellaneous action  8/28/2017 DONE
DetailsTim Frost
Emailed contractor in regards to failed review.
Application received  8/24/2017 DONE
Application submitted via PDS Online on Aug 24 2017 12:00PM