INSP-Final Inspection | 12/27/2017 | 12/28/2017 | 12/28/2017 | A | PASS |
Jim Page
|
|
|
Final fire sprinkler inspection complete.
|
INSP-Final Inspection | 12/26/2017 | 12/26/2017 | 12/26/2017 | P | FAIL |
Jim Page
|
|
|
Fire bell needs to be relocated to be visible from the address side of the street. Irrigation needs to shut off when flow switch activates, system was not wired for irrigation isolation at time of inspection.
|
INSP-Final Inspection | 12/18/2017 | 12/19/2017 | 12/19/2017 | P | CANC |
Jim Page
|
|
|
Call Jake before heading out, thanks! Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello Inspection cancelled from web by: Anthony Minichiello
|
INSP-Final Inspection | 12/13/2017 | 12/14/2017 | 12/13/2017 | A | CANC |
Jim Page
|
|
|
Please call Jake before heading out, thank you! Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello Inspection cancelled from web by: Anthony Minichiello
|
INSP-Final Inspection | 12/11/2017 | 12/13/2017 | 12/13/2017 | A | CANC |
Jim Page
|
|
|
Please call Jake before heading out, thanks! Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello Inspection cancelled from web by: Anthony Minichiello
|
INSP-Sprinkler Rough-in/Hydro | 9/18/2017 | 9/18/2017 | 9/18/2017 | P | PASS |
Jim Page
|
|
|
Rough to cover inspection for overhead fire sprinkler piping/tenting complete, approved for cover.
|
Plan Modification Accepted | | | 9/18/2017 | | DONE |
|
|
|
|
Plan assigned to (Tim) | 9/18/2017 | | 9/18/2017 | | DONE |
Tim Frost
|
|
|
|
Sprinkler Plan Check | 9/18/2017 | | 9/18/2017 | | PASS |
Tim Frost
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/18/2017 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 9/18/2017 | | DONE |
|
|
|
Do not re-issue- (plan mod)
|
CHANGE STATUS TO (ISS) | | | 9/18/2017 | | DONE |
|
|
|
|
(F) Reprint permit | | | 9/18/2017 | | DONE |
|
|
|
|
INSP-Sprinkler Rough-in/Hydro | 9/13/2017 | 9/14/2017 | 9/14/2017 | P | FAIL |
Troy Cobbley
|
|
|
Contractor needs to contact plan review and discuss need for as-builts or plan mods due to additional fittings and pipe routing. No tenting is installed. I noted two heads too close to one another. No piping to be covered. Also verification is needed for irrigation piping connection.
|
Issue and Print Permit | | | 9/5/2017 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 9/5/2017 | | 9/5/2017 | | DONE |
Tiffany Carson-Herker
|
|
|
|
Sprinkler Plan Check | 9/1/2017 | | 9/1/2017 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/1/2017 | | DONE |
Tim Frost
|
|
|
|
Permit Ready to Issue | | | 9/1/2017 | | DONE |
|
|
|
all met
|
Intake Approval | | | 8/31/2017 | | PASS |
|
|
|
|
Plan assigned to (Tim) | 8/31/2017 | | 8/31/2017 | | DONE |
Tim Frost
|
|
|
|
Sprinkler Plan Check | 8/31/2017 | | 8/31/2017 | | FAIL |
Tim Frost
|
|
|
|
1st review completed | | | 8/31/2017 | | FAIL |
Tim Frost
|
|
|
|
Miscellaneous action | | | 8/31/2017 | | DONE |
Tim Frost
|
|
|
Emailed contractor in regards to failed review.
|
Application received | | | 8/30/2017 | | DONE |
|
|
|
Application submitted via PDS Online on Aug 30 2017 9:44AM
|