INSP-Final Inspection | 3/30/2018 | 4/2/2018 | 4/2/2018 | A | PASS |
Troy Cobbley
|
|
|
permit finaled
RICK FRY Phone #: ###-#### Inspection requested via web by Nathan Stenquist
|
INSP-Final Inspection | 3/29/2018 | 3/30/2018 | 3/30/2018 | A | CANC |
Troy Cobbley
|
|
|
Unable to test the system due to fire alarm interface issues.
RICK FRY Phone #: ###-#### Inspection requested via web by Nathan Stenquist
|
INSP-Final Inspection | 3/14/2018 | 3/15/2018 | 3/15/2018 | A | PART |
Troy Cobbley
|
|
|
I verified the basement wet system tamper switches functioned/reported and I also verifed that the forward flush test passed
Rick Fry Phone #: ###-#### Inspection requested via web by Nathan Stenquist
|
INSP-Final Inspection | 2/28/2018 | 3/1/2018 | 2/28/2018 | A | CANC |
Troy Cobbley
|
|
|
Fire final for 10 AM. Rick Fry Phone #: ###-#### >> Inspection requested via web by Nathan Stenquist Inspection cancelled from web by: Nathan Stenquist
|
Plan Modification Accepted | | | 2/8/2018 | | DONE |
|
|
|
|
Plan assigned to (Tim) | 2/8/2018 | | 2/8/2018 | | DONE |
Tim Frost
|
|
|
|
Sprinkler Plan Check | 2/8/2018 | | 2/8/2018 | | PASS |
Tim Frost
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 2/8/2018 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 2/8/2018 | | DONE |
|
|
|
waiting to see if fees are due for the plan mod-called Tim F-please do not re issue
|
CHANGE STATUS TO (ISS) | | | 2/8/2018 | | DONE |
|
|
|
as per Tim F no fees due for the plan mod
|
(F) Reprint permit | | | 2/8/2018 | | DONE |
|
|
|
|
INSP-Sprinkler Rough-in/Hydro | 2/5/2018 | 2/6/2018 | 2/6/2018 | A | PASS |
Troy Cobbley
|
|
|
The second floor and pre-action system 200lb hydro tests passed.
|
INSP-Sprinkler Rough-in | 1/31/2018 | 2/1/2018 | 2/1/2018 | A | PASS |
Troy Cobbley
|
|
|
24 hour air test passed. The remaining second floor piping rough-in passed. Piping can be covered. Plan Mod needed showing pipe routing changes for 3" mains and Pre-action system.
|
INSP-Sprinkler Rough-in | 1/31/2018 | 1/31/2018 | 1/31/2018 | P | PART |
Troy Cobbley
|
|
|
24 hour air test started at 9:00am with 51psi on the guage
|
INSP-Sprinkler Rough-in | 1/18/2018 | 1/19/2018 | 1/19/2018 | A | PASS |
Troy Cobbley
|
|
|
See the revised city approved plans for the area on the 2nd floor where the piping can be covered. I noted one missing EQ brace.
Nathan Stenquist. RI INSP for the second floor East side. Phone #: ###-#### Inspection requested via web by Nathan Stenquist
|
Plan Modification Accepted | | | 1/12/2018 | | DONE |
|
|
|
|
Miscellaneous action | | | 1/12/2018 | | PEND |
|
|
|
*** FIELD INSPECTOR ***
Do NOT final this permit. A detection system for the server room is required to be submitted, approved and tested prior to the final. See revised drawings. The preaction system supplies (3) rooms. One on the first floor and two on the second floor. A total of six sprinkles.
|
Sprinkler Plan Check | 1/12/2018 | | 1/12/2018 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 1/12/2018 | | DONE |
Tim Frost
|
|
|
|
Permit Ready to Issue | | | 1/12/2018 | | DONE |
|
|
|
Plan Mod Approved
DO NOT REISSUE
|
Issue and Print Permit | | | 1/12/2018 | | |
|
|
|
|
(F) Reprint permit | | | 1/12/2018 | | DONE |
|
|
|
|
INSP-Sprinkler Rough-in/Hydro | 12/13/2017 | 12/13/2017 | 12/13/2017 | P | PASS |
Troy Cobbley
|
|
|
OH hydro for the first floor passed
|
INSP-Sprinkler Rough-in | 12/5/2017 | 12/5/2017 | 12/5/2017 | P | PASS |
Troy Cobbley
|
|
|
The corrections for the piping on the previous inspection have been performed and the piping can be covered.
Rick Phone #: ###-####
|
INSP-Sprinkler Rough-in | 11/22/2017 | 11/22/2017 | 11/22/2017 | P | PASS |
Troy Cobbley
|
|
|
See the city approved plans for locations inspected today where the rough-in was passed. I noted missing siesmic bracing for the branchlines, one missing lateral main bracing and one pendant head overspaced.
Rick Phone #: ###-####
|
INSP-Sprinkler Rough-in/Hydro | 11/16/2017 | 11/16/2017 | 11/16/2017 | P | FAIL |
Troy Cobbley
|
|
|
No approved plans on site. No inspection performed
Rick Phone #: ###-####
|
Sprinkler Plan Check | 9/22/2017 | | 9/22/2017 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/22/2017 | | DONE |
Tim Frost
|
|
|
|
Permit Ready to Issue | | | 9/22/2017 | | DONE |
Christina Prado
|
|
|
All requirements met
|
Issue and Print Permit | | | 9/22/2017 | | DONE |
|
|
|
|
Intake Approval | | | 9/18/2017 | | PASS |
|
|
|
|
Plan assigned to (Tim) | 9/18/2017 | | 9/18/2017 | | DONE |
Tim Frost
|
|
|
|
Application received | | | 9/14/2017 | | DONE |
|
|
|
Application submitted via PDS Online on Sep 14 2017 9:28AM
|